DC CURRENT OR VOLTAGE 4kV OR 1.5kV ISOLATION TRANDUCERS

SELECTION GUIDE
M100-DA1 DC current input 4kV isolation
M100-DV1 DC voltage 20 mV...11.9V input 4kV isolation
M100-DV2 DC voltage 12 V....600 V input 4kV isolation

M100-DA1I DC current input 1.5kV isolation
M100-DV1I DC voltage 20mV...11.9V input 1.5kV isolation
M100-DV2I DC voltage 12 V...600V input 1.5kV isolation


TYPICAL APPLICATIONS
These isolators isolate the DC input signal from the DC
Output signal, which is directly proportional to the input
signal. There are two levels of isolation offered, the
M100-DA1 / DV1 / DV2 have 4kV isolation and the
M100-DA1I / DV1I / DV2I have 1.5kV isolation.
A wide range of both D.C. Current and voltage inputs are
offered.
Typically these isolators can be used to prevent earth
loops, which occur when a measuring source, that is
earthed, is connected to a computer or data logger that is
also earthed. Another common use is to provide isolation
on the inputs to a PLC.
All of the above isolators have either A.C. or D.C.
Auxiliaries which means they have an advantage over loop
powered units, in that if for any reason the output lead
should become disconnected, the input will not be
saturated.

OPTIONS
1. Non standard inputs / outputs only as far as technically
acceptable.
2. A.C. Auxiliary in range 57.7 to 450 volts
3. Calibration at temperature other than 23°C

TECHNICAL INFORMATION
INPUT
Rated value In ± 0-1mA...10A M100-DA1 / DA1I
Voltage drop 20mV
Rated value Un ± 20mV......11.9V M100-DV1 / DV1I
Impedance 100 kOhm / volt
Rated value Un ± 12 V.......600 V M100-DV2 / DV2I
Impedance 10 kOhm / volt
Working range ± 125% In
Overload continuous 4 x In M100-DA1 (upto 20A max)
Overload continuous 1.5 x Un M100-DV1 / DV2
OUTPUT
Rated value mA 0-1/5/10/20 & 4-20mA
Load resistance 12/2.4/1.2/0.6 kOhm
Rated value volts 0-5 / 10 & 1-5 V
ADJUSTMENT
Zero ± 2%
Span ± 10%
AUXILIARY
A.C. Voltage 115 / 230 / 400 V (± 25% / 45-65
Hz / < 2VA)
D.C. Voltage 24 / 48 / 110 V (± 20% /
galvanically isolated / <3W)
WEIGHT & CASE SIZE Approx. 0.4 kg. 55mm case
INSULATION
M100-DA1/DV1/DV2 4kV As shown in general
specification see page 3.
M100-DA1I/DV1I/DV2I Test voltage 1.5kV RMS 50Hz 1 min
between input / case / output, rest of
specification as shown in general
specification see page 3

ORDERING INFORMATION
Product code Input In Output Aux Freq. Options
M100-DA1I 1mA 4-20mA 230V 50Hz