SELECTION
GUIDE
M100-AA1 1 ph. self powered
ave. sensing RMS calibrated
M100-AL1 1 ph. aux. powered
ave. sensing RMS calibrated
M100-AR1 1 ph. aux powered
true RMS sensing RMS cal.
M100-AA3 3 ph. self powered
ave. sensing RMS calibrated
M100-AL3 3 ph. aux powered
ave. sensing RMS calibrated
TYPICAL APPLICATIONS
The M100 series current
transducers are designed to measure
A.C. Current in single
and 3 phase systems. They convert the
A.C. signal to a D.C.
Output that is directly proportional to
the input signal.
The M100-AA1 AA3 are
self powered (i.e. no auxiliary
required) average sensing
RMS calibrated current
transducers, mA and voltage
outputs are available.
The M100-AL1 AL3 are
average sensing RMS calibrated, live
zero current transducers.
Auxiliary is required to provide
power, so that 4mA output
signal is present, when the input is
zero.
The M100-AR1 is true
RMS sensing RMS calibrated allowing
measurement of distorted
waveforms of up to 9th harmonic
with a crest factor of
5. The AR1 is typically used in current
measurement where distorted
waveform is common, such as
thyristor drives
The above units are used
to measure current in energy
management systems, switchboards,
generator and telemetery
controls. Isolation of
4kV is provided between the input and
output signal, allowing
the output to be fed to conventional
analogue meters, digital
meters, PLC, and computer systems.
ORDERING INFORMATION
Product Code Input In
Output Aux Freq. Options
M100-AL1 5A 4-20mA 230V
50Hz
OPTIONS
1. Non standard inputs
/ outputs only as far as technically
acceptable.
2. A.C. Auxiliary in
range 57.7 to 450 volts
3. Calibration at nominal
Hz 35.....450Hz
4. Calibration at temperature
other than 23°
|
|
|
TECHNICAL
SPECIFICATION
INPUT
Rated value In 1 or 5
Amp C.T. connected
0.5-10 Amp direct connected
Power consumption <1
VA (AA1, AA3)
<0.2 VA (AL1, AL3, AR1)
Working range 10-125%
In (AA1, AA3)
0-125% In (AL1, AL3,
AR1)
Rated Frequency 50 /
60 / 400 Hz
Frequency influence 0.005
% / Hz
Overload continuous 4
x In
Overload for 1 sec. 50
x In
OUTPUT
Rated value mA 0-1/5/10/20mA
(AA1, AA3)
Rated value mA 0-1/5/10/20
& 4-20mA (AR1)
Rated value mA 4-20mA
(AL1 AL3)
Rated value volts 0-5
/ 10 V (AA1 AA3)
Rated value volts 0-5
/ 10 & 1-5 V (AR1)
Rated value volts 1-5
V (AL1 AL3)
ADJUSTMENT
Zero No adjustment (AA1
AA3)
Zero ± 2% (AR1, AL1 AL3)
Span ± 10% (AA1, AR1,
AL1 AA3
AL3)
AUXILIARY
A.C. Voltage 115 / 230
/ 400 V (± 25% /
45-65 Hz / < 2VA)
D.C. Voltage 24 / 48
/ 110 V (± 20% /
galvanically isolated
/ <3 W)
Note M100-AA1 AA3 are
self
powered
WEIGHT & CASE
M100-AA1 Approx. 0.3
kg. 55mm case
M100-AL1,AR1 Approx.
0.4 kg. 55mm case
M100-AA3 Approx. 0.6
kg. 100mm case
M100-AL3 Approx. 0.7
kg. 100mm case
|
|