AC VOLTAGE TRANSDUCER

TECHNICAL SPECIFICATION
INPUT
Rated value Un 57.8 <100 / 110 <600 V
Power consumption <1.5 VA (VA1, VA3)
<1 VA (VL1, VL3, VR1)
Working range 15-125% Un (VA1, VA3)
0-125% Un (VL1, VL3, VR1)
Rated Frequency 50 / 60 / 400 Hz
Frequency influence 0.005 % / Hz
Overload continuous 1.5 x Un
Overload for 1 sec. 4 x Un (VL1 VL3 VR1 )
2 x Un (VA1 VA3)

OUTPUT
Rated value mA 0-1/5/10/20mA (VA1, VA3)
Rated value mA 1/5/10/20 & 4-20mA (VR1)
Rated value mA 4-20mA (VL1)

Rated Value volts 0-5 / 10 V (VA1, VA3)
Rated value volts 0-5 / 10 & 1-5 V (VR1)
Rated value volts 1-5 V (VL1 VL3)

ADJUSTMENT
Zero No adjustment (VA1,VA3)
Zero ± 2% (VR1,VL1)
Span ± 10% (VA1,VA3,VR1,VL1,VL3)

AUXILIARY
A.C. Voltage 115 / 230 / 400 V
(± 25% / 45-65Hz / <2 VA)
D.C. Voltage 24 / 48 / 110 V (± 20% /
galvanically isolated / < 3 W)
Note M100-VA1 & VA3 are self
powered.
WEIGHT & CASE SIZE
M100-VA1 Approx. 0.3 kg. 55mm case
M100-VL1,VR1 Approx. 0.4 kg. 55mm case
M100-VA3 Approx. 0.6 kg. 100mm case
M100-VL3 Approx. 0.7 kg. 100mm case


SELECTION GUIDE
M100-VA1 1 ph. self powered ave. sensing RMS calibrated
M100-VL1 1 ph. aux powered ave. sensing RMS calibrated
M100-VR1 1 ph. aux powered true RMS sensing RMS cal.
M100-VA3 3 ph. self powered ave. sensing RMS calibrated
M100-VL3 3 ph. aux powered ave. sensing RMS calibrated

TYPICAL APPLICATIONS
The M100 series voltage transducers are designed to measure
A.C. Voltage in single and 3 phase system. They convert the
A.C. Signal to a D.C. Output that is directly proportional to
the input signal.
The M100-VA1 VA3 are self powered (i.e. no auxiliary
required) average sensing RMS calibrated voltage
transducers, mA and voltage outputs are available.
The M100-VL1 VL3 are average sensing RMS calibrated, live
zero voltage transducers. Auxiliary is required to provide
power so that 4mA output signal is present when the input is
zero.
The M100-VR1 is true RMS sensing RMS calibrated allowing
measurement of distorted waveforms of up to 9th harmonic
with a crest factor of 5. The VR1 is typically used in voltage
measurement where distorted waveform is common such as
thyristor drives.
The above units are used to measure voltage in energy
management systems, switchboards, generator and telemetery
controls. Isolation of 4kV is provided between the input and
output signal, allowing the ouput to be fed to conventional
analogue meters, digital meters, PLC, and computer systems.

ORDERING INFORMATION
Product Code Input In Output Aux Freq. Options
M100-VA1 230V 4-20mA 230V 50Hz

OPTIONS
1. Non standard inputs / outputs only as far as technically
acceptable.
2. A.C. Auxiliary in range 57.7 to 450 volts
3. Calibration at nominal Hz 35.....450Hz
4. Calibration at temperature other than 23°C