TECHNICAL
SPECIFICATION
INPUT
Rated value Un 57.8 <100
/ 110 <600 V
Power consumption <1.5
VA (VA1, VA3)
<1 VA (VL1, VL3, VR1)
Working range 15-125%
Un (VA1, VA3)
0-125% Un (VL1, VL3,
VR1)
Rated Frequency 50 /
60 / 400 Hz
Frequency influence 0.005
% / Hz
Overload continuous 1.5
x Un
Overload for 1 sec. 4
x Un (VL1 VL3 VR1 )
2 x Un (VA1 VA3)
OUTPUT
Rated value mA 0-1/5/10/20mA
(VA1, VA3)
Rated value mA 1/5/10/20
& 4-20mA (VR1)
Rated value mA 4-20mA
(VL1)
Rated Value volts 0-5
/ 10 V (VA1, VA3)
Rated value volts 0-5
/ 10 & 1-5 V (VR1)
Rated value volts 1-5
V (VL1 VL3)
ADJUSTMENT
Zero No adjustment (VA1,VA3)
Zero ± 2% (VR1,VL1)
Span ± 10% (VA1,VA3,VR1,VL1,VL3)
AUXILIARY
A.C. Voltage 115 / 230
/ 400 V
(± 25% / 45-65Hz / <2
VA)
D.C. Voltage 24 / 48
/ 110 V (± 20% /
galvanically isolated
/ < 3 W)
Note M100-VA1 & VA3
are self
powered.
WEIGHT & CASE SIZE
M100-VA1 Approx. 0.3
kg. 55mm case
M100-VL1,VR1 Approx.
0.4 kg. 55mm case
M100-VA3 Approx. 0.6
kg. 100mm case
M100-VL3 Approx. 0.7
kg. 100mm case
|
|
|
|
SELECTION
GUIDE
M100-VA1 1 ph. self powered
ave. sensing RMS calibrated
M100-VL1 1 ph. aux powered
ave. sensing RMS calibrated
M100-VR1 1 ph. aux powered
true RMS sensing RMS cal.
M100-VA3 3 ph. self powered
ave. sensing RMS calibrated
M100-VL3 3 ph. aux powered
ave. sensing RMS calibrated
TYPICAL APPLICATIONS
The M100 series voltage
transducers are designed to measure
A.C. Voltage in single
and 3 phase system. They convert the
A.C. Signal to a D.C.
Output that is directly proportional to
the input signal.
The M100-VA1 VA3 are
self powered (i.e. no auxiliary
required) average sensing
RMS calibrated voltage
transducers, mA and voltage
outputs are available.
The M100-VL1 VL3 are
average sensing RMS calibrated, live
zero voltage transducers.
Auxiliary is required to provide
power so that 4mA output
signal is present when the input is
zero.
The M100-VR1 is true
RMS sensing RMS calibrated allowing
measurement of distorted
waveforms of up to 9th harmonic
with a crest factor of
5. The VR1 is typically used in voltage
measurement where distorted
waveform is common such as
thyristor drives.
The above units are used
to measure voltage in energy
management systems, switchboards,
generator and telemetery
controls. Isolation of
4kV is provided between the input and
output signal, allowing
the ouput to be fed to conventional
analogue meters, digital
meters, PLC, and computer systems.
ORDERING INFORMATION
Product Code Input In
Output Aux Freq. Options
M100-VA1 230V 4-20mA
230V 50Hz
OPTIONS
1. Non standard inputs
/ outputs only as far as technically
acceptable.
2. A.C. Auxiliary in
range 57.7 to 450 volts
3. Calibration at nominal
Hz 35.....450Hz
4. Calibration at temperature
other than 23°C
|
|
|
|