SELECTION
GUIDE
M100-DS1 DC current 1
input
M100-DS2 DC current 2
inputs
M100-DS3 DC current 3
inputs
M100-DS4 DC current 4
inputs
TYPICAL APPLICATIONS
The M100-DS series of
summation transducer take up to four inputs and provide an output signal
directly proportional to the sum of the inputs. A typical application
is the summation of total kW of four
separate generating sets
e.g. the four individual kW readings are provided by M100-WA4 transducers
with 0-1mA output signals. The M100-DS4 summates the four 0-1mA signals
and provides a single output signal that is directly proportional the
sum of the total kW of all four generators.
It is important to note
the following when using summation transducers, to ensure the correct
reading is obtained :-
The current and voltage
ratios must be identical otherwise
the subsequent summation
will be meaningless.
|
|
|
TECHNICAL
SPECIFICATIONS
INPUT
Rated value In ± 0-1mA...20mA
Voltage drop 20mV
Working range ±125%
Overload continuous 4
x In
Overload continuous 1.5
x Un
OUTPUT
Rated value mA 0-1/5/10/20
& 4-20mA
Load resistance 12/2.4/1.2/0.6
kOhm
Rated value volts 0-5
/ 10 & 1-5 V
ADJUSTMENT
Zero ± 2%
Span ± 10%
AUXILIARY
A.C. Voltage 115 / 230
/ 400 V (± 25% / 45-65Hz / < 2VA)
D.C. Voltage 24 / 48
/ 110 V (± 20% /galvanically isolated / <3W)
WEIGHT & CASE SIZE Approx.
0.4 kg. 55mm case
OPTIONS
1. Non standard inputs
/ outputs only as far as technically acceptable.
2. A.C. Auxiliary in
range 57.7 to 450V
3. Calibration at temperature
other than 23°C
|
|