SELECTION
GUIDE
M100-FA1 Self powered
true zero outputs
M100-FL1 Auxiliary powered
live zero outputs
M100-FX1 Auxiliary powered
true zero outputs
TYPICAL APPLICATIONS
The M100 series of frequency
transducers are designed to
measure frequency in
single and 3 phase systems. The A.C.
Input is converted to
a D.C. Output, that is directly
proportional to the change
in input frequency within a
specified span.
The M100-FA1 is self
powered. (No auxiliary required)
The working voltage range
is 75-125% of the nominal
voltage.
The M100-FL1 is auxiliary
powered. The outputs are live
zero either 4mA or 1
volt. The auxiliary enables the working
voltage range to be 15-125%.
The M100-FX1 is essentially
the same as the FA1 but an
auxiliary is provided
to enable the unit to have a working
voltage range of 15-125%.
All types of the above
frequency transducers are typically
used to monitor and control
frequency in such applications
as 3 phase mains supplies,
A.C. Generating sets and process
control etc.
ORDERING INFORMATION
Product code Input Hz
Output Aux Freq. Options
M100-FL1 45-55Hz 4-20mA
230V 50Hz
OPTIONS
1. Non standard inputs
/ outputs only as far as technically
acceptable.
2. A.C. Auxiliary in
range 57.7 to 450 volts
3. Calibration at temperature
other than 23°C
|
|
|
TECHNICAL
SPECIFICATION
INPUT
Rated value Un 57.8 <
600V
Power consumption <1.5
VA (FA1)
<1 VA (FL1 FX1)
Working range 75-125%
Un (FA1)
15-125% Un (FL1 FX1)
Measuring range 45-55
/ 45-65 / 55-65
/ 360-440Hz
Overload continuous 1.5
x Un
Overload for 1 sec. 2
x Un
OUTPUT
Rated value mA 0-1 /
5 / 10 / 20mA (FA1 FX1)
Rated value mA 4-20mA
(FL1)
Rated value volts 0-5
/ 10 V (FA1 FX1)
Rated value volts 1-5
V (FL1)
ADJUSTMENT
Zero No adjustment
Span No adjustment
AUXILIARY
A.C. Voltage 115 / 230
/ 400 V
(± 25% / 45-65 Hz /
< 2 VA)
D.C. Voltage 24 / 48
/ 110 V ( ±20% /
galvanically isolated
/ <3W)
Note M100-FA1 is self
powered
WEIGHT & CASE SIZE Approx.
0.4kg. 55mm case
|
|