PHASE ANGLE TRANSDUCER

SELECTION GUIDE
M100-PA1 Single phase 4 quadrants
M100-PA2 3 phase 3 or 4 wire balanced 2 quadrants
M100-PA3 3 phase 3 or 4 wire balanced 4 quadrants
M100-PV1 Single phase 4 quadrants phase angle
between two voltages

TYPICAL APPLICATIONS
The M100-PA series of phase angle transducers measure
the phase angle between current and voltage. They can be
used on single and 3 phase 3 or 4 wire balanced systems.
Ideal for optimising power factor correction.
The M100-PV2 measures the phase angle between two
voltage supplies and provides a D.C. Output signal
proportional to the phase angle between the voltages.

ORDERING INFORMATION
Product code I/P In Un O/P Range Aux. Freq.Opt.
M100-PA2 5Amp 400V ± 45° 120V 60Hz

OPTIONS
1. Non standard inputs / outputs only as far as technically
acceptable.
2. A.C. Auxiliary in range 57.7 to 450 volts
3. Calibration at nominal Hz 35.....450Hz
4. Calibration at temperature other than 23°C

TECHNICAL SPECIFICATION
INPUT
Rated value In 1 or 5 Amp C.T. connected
0.5-10 Amp direct connected
Rated value Un 57.8 < 600 volt
Power consumption <1 VA voltage (aux powered)
<2.5 VA voltage (self powered)
<0.2 VA current
Working range 15-125% Un auxiliary powered
75-125% Un self powered
10-150% In
Measuring range ± 45 / 60 / 90 / 180° M100-PA1
± 45 / 60° M100-PA2
± 90 / 180° M100-PA3
Rated Frequency 50 / 60 / 400 Hz
Frequency influence 0.005 % / Hz
Overload continuous 4 x In 1.5 x Un
Overload for 1 sec. 50 x In 2 x Un
ACCURACY ± 1 Degree
OUTPUT
Rated value mA 0-1/5/10/20 & 4-20mA
Rated Value Volts 0-5 / 10 & 1-5 V
ADJUSTMENT
Zero ± 2%
Span ± 10%
AUXILIARY
A.C. Voltage 115 / 230 / 400 V (± 25% / 45-65
Hz / < 2VA)
D.C. Voltage 24 / 48 / 110 V (± 20%
galvanically isolated / <3W)
WEIGHT & CASE SIZE Approx. 0.6 kg. 100mm case