SELECTION GUIDE
M100-AX1 1 ph. aux.
powered ave. sensing RMS calibrated
M100-AX3 3 ph. aux powered
ave. sensing RMS calibrated
M100-AAS 3 ph. summation
self powered
M100-ALS 3 ph. summation
auxiliary powered
TYPICAL
APPLICATIONS
The M100-AX1 and AX3 are essentially the same as the M100-AA1 and AA3,
but they have auxiliaries which allows the working range to be 0-125%
rather than 10-125%. Used where the average sensing of current is required
from 0-125% of the nominal current.
The M100-AAS and M100-ALS
are A.C. Current summation transducers. Both can have up to 3 inputs
of either 1, 5 or 10 amps. These inputs are summed by the transducer
and one D.C. Output is provided, which is proportional to the sum of
the inputs.
The M100-AAS is self
powered with a range of 10-125% , the M100-ALS is auxiliary powered
and provides a 4-20mA output with a working range of 0-125%. Typical
application is to measure the total current in a 3 phase system and
display it via one meter. For example, if a 3 phase system has 3 current
transformers 2500/5 then a moving coil meter could be connected to a
M100-AAS scaled 0-7500.
Note the C.T.s must
all have the same ratio or the output from the transducer will not be
the sum of the total current in the system.
ORDERING INFORMATION
Product Code Input In
Output Aux Freq. Options
M100-ALS 3 x 5A 0-20mA
115V 50Hz Cal. 40°C
OPTIONS
1. Non standard
inputs / outputs only as far as technically
acceptable.
2. A.C. Auxiliary in
range 57.7 to 450 volts
3. Calibration at nominal
Hz 35.....450Hz
4. Calibration at temperature
other than 23°C
|
|
|
TECHNICAL
SPECIFICATION
INPUT
Rated value In 1 or 5
Amp C.T. connected
0.5-10 Amp direct connected
Power consumption <0.2
VA (AX1, AX3 ALS)
<1 VA (AAS)
Working range 0-125%
In (AX1, AX3, ALS)
10-125% In (AAS)
Rated Frequency 50 /
60 / 400 Hz
Frequency influence 0.005
% / Hz
Overload continuous 4
x In
Overload for 1 sec. 50
x In
OUTPUT
Rated value mA 0-1/5/10/20mA
(AX1,AX3,AAS)
Rated value mA 4-20mA
(ALS)
Rated Value Volts Not
available on (AAS)
Rated Value Volts 1-5
V (ALS)
Rated Value Volts 0-5
/ 10V (AX1,AX3)
ADJUSTMENT
Zero No adjustment (AX1,
AX3, AAS)
Zero ± 2% (ALS)
Span ± 10% (AX1, AX3,
ALS)
AUXILIARY
A.C. Voltage 115 / 230
/ 400 V (± 25% /
45-65 Hz / < 2VA)
D.C. Voltage 24 / 48
/ 110 V (± 20%
galvanically isolated
/ <3W)
Note M100-AAS is self
powered
WEIGHT & CASE SIZE
M100-AX1 Approx. 0.4
kg. 55mm case
M100-AAS Approx. 0.6
kg. 100mm case
M100-ALS,AX3 Approx.
0.7 kg. 100mm case |
|