DC LINEAR INTEGRATOR TRANSDUCER

TECHNICAL SPECIFICATION
INPUT
Rated value In 0-1 / 5 / 10 / 20 & 4-20 mA
Voltage drop 20mV
Rated value Un 0-20mV.....10V
Impedance 100 kOhm / V
Working range 0-125%
Overload continuous 1.5 x Un 4 x In
OUTPUT
Contact volt free closure
Pulse rate 100.......5000 pulse/hr
Pulse width 250 msec
RELAY
Voltage 50 V DC / 250 V AC
Rating 10W
Contact material Ruthonium
Initial resistance 200 mOhm
Initial capacitance 0.4 pF
Electrical life 5 x 106 (250 V DC / 10mA /
resistance load)
Test voltage coil to contacts 4kV
ADJUSTMENT
Zero ± 2%
Span ± 10%
AUXILIARY
A.C. Voltage 115 / 230 / 400 V
(± 25% / 45-65Hz / <2 VA)
D.C. Voltage 24 / 48 / 110 V ± 20%
galvanically isolated / < 3 W)
WEIGHT & CASE SIZE Approx. 0.4 kg. 55mm case

ORDERING INFORMATION
Product Code Input In Pulse Rate Aux. Freq. Opt.
M100-DI1 10mA 100/hour 230V 50Hz


SELECTION GUIDE
M100-DI1 Single relay output
M100-DI2 Double relay output


TYPICAL APPLICATIONS
The M100-DI1 is a linear integrator which accepts D.C.
Inputs, and integrates the input with respect to time. An ouput
is provided via a relay which gives a pulsed output, the
frequency of which is directly proportional to the amplitude
of the input signal.
One of the main uses of the M100-DI1 is the measurement of
Watt and Kilowatt hour. This is achieved by feeding the output
of a watt transducer (M100-WA series) into the M100-DI1.
The input signal is integrated against time and the resulting
output pulses from the relay are proportional to the kW.h
being consumed. These pulses then can be fed to an
electromechanical counter, digital counter or a computer,
where the kW.h consumed can be stored. Another use is the
measurement of Ampere hours.
The M100- DI2 is the same as M100-DI1 with the additional
feature of having 2 relay outputs, this allows the user to feed
one set of pulses to a counter on a switchboard whilst feeding
the other set of pulses to a remote computer in a control room.

OPTIONS
1. Non standard inputs / outputs only as far as technically
acceptable.
2. A.C. Auxiliary in range 57.7 to 450 volts
3. Calibration at temperature other than 23°C