SELECTION
GUIDE
M100-RPN Resistance measurement
TYPICAL APPLICATIONS
The M100-RPN is designed
to measure the resistance of 3 wire potentiometers, where the resistance
value is proportional to the position of the wiper of the potentiometer.
The output value from the M100-RPN is directly proportional to the resistance
value at the wiper.
A typical application
is monitoring remote resistance of potentiometer used in manual valve
control.
OPTIONS
1. Non standard inputs
/ outputs only as far as technically acceptable.
2. A.C. Auxiliary in
range 57.7 to 450V
3. Calibration at temperature
other than 23°C
ORDERING INFORMATION
Product Code:Input:Output:Aux:Freq
M100-DS1 1mA 4-20mA 230V
50Hz
|
|
TECHNICAL
SPECIFICATION
INPUT
Rated range min. 100
ohms.... max. 50 kOhms
Sensor current min. 20uA....
max. 10mA
Sensor voltage 1 Volt
Working range 0-100%
RN
OUTPUT
Rated value mA 1/5/10/20
& 4-20mA
Rated value volts 0-5
/ 10 & 1-5 V
ADJUSTMENT
Zero 0-35%
Span 65-100%
AUXILIARY
A.C. Voltage 115 / 230
/ 400 V (± 25% / 45-65Hz / < 2VA)
D.C. Voltage 24 / 48
/ 110 V (± 20% /galvanically isolated / <3W)
WEIGHT & CASE SIZE Approx.
0.4 kg. 55mm case
NOTE
No isolation is provided
between input and output
|
|