SELECTION
GUIDE
M100-RTD RTD temperature
measurement
TYPICAL APPLICATIONS
The M100-RTD monitors
the resistance of either 100 Ohm Platinum, or 120 Ohm Nickel. The RTDs
resistance increase as the temperature rises, this resistance change is
detected by the M100-RTD, which provides an output corresponding to the
temperature being measured.
The temperature versus
resistance values, are provided by the supplier of the RTD used.
RTD measurement of temperature
is used in large transformers and large motors, to ensure winding temperatures
do not rise to a level that would damage the winding.
ORDERING INFORMATION
Product Code:RTD:Temp:Output:Auxiliary:Frequency
M100-RTD Pt 100 0-250°C
5 mA 230V 50Hz
OPTIONS
1. Non standard inputs
/ outputs only as far as technically acceptable.
2. A.C. Auxiliary in
range 57.7 to 450 volts
3. Calibration at temperature
other than 23°C
|
|
|
TECHNICAL
SPECIFICATION
INPUT
2 or 3 wire input
Platinum Pt 100 Ohm RTD
min. span 20 Ohms ...max. span 200 Ohms
Nickel Ni 120 Ohm RTD
min. span 24 Ohms....max. span 240 Ohms
OUTPUT
Rated value mA - 0-1/5/10/20
& 4-20mA
Rated value volts - 0-5
/ 10 & 1-5 V
ACCURACY
Class ± 0.5%
ADJUSTMENT
Zero - ± 2%
Span - ± 10%
AUXILIARY
A.C. Voltage - 115 /
230 / 400 V (± 25% / 45-65 Hz / < 2VA)
D.C. Voltage - 24 / 48
/ 110 V (± 20% / galvanically isolated / <3W)
WEIGHT & CASE SIZE Approx.
0.3 kg. 55mm case
NOTE
No isolation is provided
between input and output
|
|