M100-TAP Resistance measurement
TYPICAL APPLICATIONS
The M100-TAP measures
the value of resistance on tap position changers, typically used on high
voltage transformers. Each position on the selector has an equal value
of resistance so that as the tap position is increased or decreased the
value of resistance increases or decrease respectively. The M100-TAP measure
the value of this resistance and provides an output proportional to the
value of the number of taps selected.
The M100-TAP can also
be used to measure variable
resistance 2 or 3 wire
systems.
ORDERING INFORMATION
Product Code:No. Of Taps
Output: Aux.:Frequency
M100-TAP 10 5 mA 230V
50Hz
OPTIONS
1. Non standard inputs
/ outputs only as far as technically acceptable.
2. A.C. Auxiliary in
range 57.7 to 450 volts
3. Calibration at temperature
other than 23°C
|
|
TECHNICAL
SPECIFICATION
INPUT
Rated range - min. 100
ohms.... max. 20 kOhms
Sensor current - min.
50uA.... max. 10mA
Sensor voltage - <1 Volt
Working range - 0-125%
Rn
OUTPUT
Rated value amps - 0-1/5/10/20
& 4-20mA
Rated value volts - 0-5
/ 10 & 1-5 V
ADJUSTMENT
Zero - ±2%
Span - ±10%
AUXILIARY
A.C. Voltage - 115 /
230 / 400 V (± 25% / 45-65 Hz / < 2VA)
D.C. Voltage - 24 / 48
/ 110 V (± 20% / galvanically isolated / <3W)
WEIGHT & CASE SIZE Approx.
0.4 kg. 55 mm case
NOTE
No isolation is provided
between input and output
|
|