AC CURRENT RELAY

SELECTION GUIDE

M200-A1U Single phase under current
M200-A1O Single phase over current
M200-A1C Single Phase combined current
M200-A3U 3 Phase under current
M200-A3O 3 Phase over current

TYPICAL APPLICATIONS

The M200 AC current relays provide current monitoring
and protection in both single and 3 phase systems. Used in
applications such as motor protection, load detection and
generator control.
Under over and combined under/over units are available.
The relay operates when the adjustable trip point is
reached. An externally adjustable time delay is provided
to prevent nuisance tripping.
As is common with all the M200 relays, on over units the
relay energises when the input signal exceeds the trip point
On under units the relay de-energises when the input signal
goes below the trip point.
A red LED indicates the state of the relay, whilst a green
LED indicates the condition of the power supply.

OPTIONS
1.Adjustable time delay max 30 seconds
2.AC Auxiliary in the range 57.7 to 480 volts
3.Calibration at nominal Hz 35 450Hz
4.Calibration at temperature other than 23º C


TECHNICAL SPECIFICATION

INPUT
Rated value In 1A or 5A from CT 0.2 to
10 Amp direct connected
Frequency 50 /60 /400 Hz
Burden <0.5 VA per phase
Overload 2 x In continuous
10 x In for 3 seconds

SETPOINT
Range Over Adjustable 40% to 120% In
Range Under Adjustable 0% to 80% In
Repeatability Better than 0.5% of full span
Differential Fixed 5%
Time Delay Adjustable 200ms to 10
seconds

AUXILIARY
AC Voltage 115/230/400V
( ± 25% /45-65 Hz / <2 VA)
DC Voltage 24 volt ( ± 20% /galvanically
isolated) <3 watt

WEIGHT& CASE SIZE
Single units Approx. 0.4kg. 55mm case
Combined units Approx. 0.6kg. 100mm case

ORDERING INFORMATION

Product Code Input Freq. Aux. Options
M200-A30 5A 50Hz 230V