SELECTION
GUIDE
M200-A1U Single phase
under current
M200-A1O Single phase
over current
M200-A1C Single Phase
combined current
M200-A3U 3 Phase under
current
M200-A3O 3 Phase over
current
TYPICAL APPLICATIONS
The M200 AC current relays
provide current monitoring
and protection in both
single and 3 phase systems. Used in
applications such as
motor protection, load detection and
generator control.
Under over and combined
under/over units are available.
The relay operates when
the adjustable trip point is
reached. An externally
adjustable time delay is provided
to prevent nuisance tripping.
As is common with all
the M200 relays, on over units the
relay energises when
the input signal exceeds the trip point
On under units the relay
de-energises when the input signal
goes below the trip point.
A red LED indicates the
state of the relay, whilst a green
LED indicates the condition
of the power supply.
OPTIONS
1.Adjustable time delay
max 30 seconds
2.AC Auxiliary in the
range 57.7 to 480 volts
3.Calibration at nominal
Hz 35 450Hz
4.Calibration at temperature
other than 23º C
|
|
|
TECHNICAL
SPECIFICATION
INPUT
Rated value In 1A or
5A from CT 0.2 to
10 Amp direct connected
Frequency 50 /60 /400
Hz
Burden <0.5 VA per phase
Overload 2 x In continuous
10 x In for 3 seconds
SETPOINT
Range Over Adjustable
40% to 120% In
Range Under Adjustable
0% to 80% In
Repeatability Better
than 0.5% of full span
Differential Fixed 5%
Time Delay Adjustable
200ms to 10
seconds
AUXILIARY
AC Voltage 115/230/400V
( ± 25% /45-65 Hz /
<2 VA)
DC Voltage 24 volt (
± 20% /galvanically
isolated) <3 watt
WEIGHT& CASE SIZE
Single units Approx.
0.4kg. 55mm case
Combined units Approx.
0.6kg. 100mm case
ORDERING INFORMATION
Product Code Input Freq.
Aux. Options
M200-A30 5A 50Hz 230V
|
|