SELECTION
GUIDE
M200-V1U Single phase
under voltage
M200-V1O Single phase
over voltage
M200-V1C Single phase
combined voltage
M200-V33U 3 phase 3 wire
under voltage
M200-V33O 3 phase 3 wire
over voltage
M200-V33C 3 phase 3 wire
combined
M200-V34U 3 phase 4 wire
under voltage
M200-V34O 3 phase 4 wire
over voltage
M200-V34C 3 phase 4 wire
combined voltage
TYPICAL APPLICATIONS
The M200 AC voltage relay
provides voltage monitoring
and protection in both
single and 3 phase systems. Used in
applications such as
mains failure, regulation of power
supplies and to protect
voltage sensitive equipment.
Under, over and combined
under/over units are available.
The relay operates when
the externally adjustable trip
point is reached. An
external differential control is
provided with adjustment
1-15%. The differential ensures
that the parameter being
measured returns to % set above
or below (depending on
whether it is under or over unit)
the trip point before
the relay returns to its original state.
As is common with al/the
M200 relays; on over units the
relay energises when
the input signal exceeds the trip
point. On under units
the relay de-energises when the
input signal goes below
the trip point.
A red LED indicates the
state of the relay, whilst a green
LED indicates the condition
of the power supply.
ORDERING INFORMATION
Product Code Input Freq
Options
M200-V34U/D 230V 50Hz
5 sec t/d
|
|
TECHNICAL
SPECIFICATION
INPUT
Rated value Un Single
phase 57.8 <500 V
Three phase 100 <500
V
Frequency 50/60/400 Hz
Burden <2.5 VA per phase
single units
<3 VA per phase combined
units
Overload 1.5x Un continuous
2 x Un for 3 seconds
SETPOINT
Range under Adjustable
75% to 100% Un
Range over Adjustable
100% to 125% Un
Repeatability Better
than 0.5% of full span
Differential Adjustable
1 to 15%
Operating time Typically
200ms
AUXILIARY
All units self powered.
WEIGHT& CASE SIZE
Single units Approx.
0.4kg. 55mm case
Combined units Approx.
0.6kg. 100 mm case
OPTIONS
1. On all of the above
units, except the combined, an
internally set time delay
is available for any value between
1 & 10 seconds. To order
use the above codes adding a D
at the end of the code,
e.g. M200-V34U/D 5 seconds (state
the fixed delay period).
2. To prevent nuisance
tripping when there is a slight
variation in the voltage
supply the following option is
available. The external
differential is replaced on the
following products with
an externally adjustable time delay.
On these units the time
delay is adjustable from 200ms to 10
seconds, and the differential
is fixed at 1%.
M200- V1X Single phase
under voltage
M200-V1Y Single phase
over voltage
M200-V1W Single phase
combined voltage
M200-V33X 3 phase 3 wire
under voltage
M200- V33Y 3 phase 3
wire over voltage
M200-V33W 3 phase 3 wire
combined voltage
M200-V34X 3 phase 4 wire
under voltage
M200- V34Y 3 phase 4
wire over voltage
M200- V34W 3 phase 4
wire combined voltage
3. Calibration at temperatures
other than 23º C
|
|