DC TRANSDUCER TRIP RELAY

SELECTION GUIDE

M200-TAU DC volts or mA under trip
M200-TAO DC volts or mA over trip
M200-TAC DC volts or mA combined trip


TYPICAL APPLICATIONS

The M200 DC transducer trips have endless
applications. As the name implies they are designed to
accept inputs from transducers and transmitters, and
provide a relay operation when the transducer signal
deviates outside a pre-set limit.
Any of the M100 series transducers can be used with the
transducer trip. A typical application is to control power
using a M100-WA5 with a 4-20mA signal fed to a M200-
TAO. For example the output goes above a pre-set limit
of 80%, the TAO relay will close, setting off an alarm or
shutting down a process.
Either DC voltage or DC current inputs can be used. As
is common with all the M200 relays, on over units the
relay energises when the input signal exceeds the trip
point and on under units the relay de-energises when the
input signal goes below the trip point.
A red LED indicates the state of the relay, whilst a green
LED indicates the condition of the power supply.

OPTIONS
1. Adjustable time delay max 30 seconds
2. AC auxiliary in the range 57.7 to 480 volts
3.Calibration at nominal Hz 35…..450Hz
4.Calibration at temperature other than 23º C


TECHNICAL SPECIFICATION

INPUT
Rated value In 0<20mA or 4- 20mA
Voltage drop 1 volt
Rated value Un 1<50 volt or 1-5 volt
Impedance 10k Ohm / Volt
Overload 2xIn 1.5x Un continuous
10x In 2x Un for 3 seconds

SETPOINT
Range Over Adjustable 40% to 120% for both
voltage and current input.
Range Under Adjustable 0% to 80% for both voltage
and current input.
Repeatability Better than 0.5% of full span
Time delay Adjustable 200 ms to 10 seconds
Differential Fixed 5%

AUXILIARY
AC Voltage 115/230/400 V
± 25% / 45-65Hz / 2VA
DC voltage 24 volt (± 20% / galvanically isolated)
<3 watt

WEIGHT & CASE SIZE
Single units Approx. 0.4kg. 55mm case
Combined unit Approx. 0.6 kg. 100mm case

ORDERING INFORMATION
Product Code Input Vn or In Aux Freq
M200-TAC 1mA 110v 50Hz