SELECTION
GUIDE
M200-TVU DC volts under
trip
M200- TVO DC volts over
trip
M200-TVC DC volts combined
trip
TYPICAL APPLICATIONS
The M200 DC voltage trips
are commonly used for monitoring battery
voltage conditions but
can be used in any application where the dc
voltage level is critical.
The user is provided with an adjustable set-point
of 0-80% on under units
and 40-120% on over units. The differential is
internally set at 5%;
no time delay is provided.
As is common with all
M200 relays, on over units the relay energises
when the input signal
exceeds the trip point and on under units the relay
de-energises when the
input signal goes below the trip point.
A red LED indicates the
state of the relay whilst a green LED indicates
the state of the power
supply.
OPTIONS
1. AC auxiliary in the
range 57.7 to 480 volts
2. Calibration at nominal
Hz 35…450Hz
3. Calibration at temperature
other than 23º C
|
|
TECHNICAL
SPECIFICATION
INPUT
Rated value Un 1<50 volt
Impedance 10k Ohm / Volt
Overload 1.5 x Un continuous
2 x Un for 3 seconds
SETPOINT
Range Over Adjustable
40% to 120%
Range Under Adjustable
0% to 80%
Repeatabiltiy Better
than 0.5% of full span
Differential Fixed 5%
AUXILIARY
AC Voltage 115/230/400V
± 25% / 45-65Hz / 2VA
DC Voltage 24 volt (±
20% / galavanically isolated)
<3 watt
WEIGHT & CASE SIZE
Single units Approx.
0.4kg. 55mm case size
Combined unit Approx.
0.6kg. 100mm case size
ORDERING INFORMATION
Product Code Input Vn
Aux Freq Options
M200-TVU 24V 110V 50Hz
|
|