SELECTION
GUIDE
M200-F1U Single or 3 phase
under frequency
M200-F1O Single or 3 phase
over frequency
M200-F1C Single or 3
phase combined frequency
TYPICAL APPLICATIONS
The M200 series frequency
relays are designed to
monitor the frequency
of a system and if the frequency
deviates outside the
adjustable pre-set limits, the relay
will operate.
Typically used in protecting
generators against over or
under speed, this is
achieved as speed is proportional to
frequency. Other uses
such as monitoring mains power
supplies, computer supplies
etc.
The user is provided
with adjustment of both the trip
point of frequency being
monitored and the differential
As is common with all
the M200 relays; on over units the
relay energises when
the input signal exceeds the trip
point. On under units
the relay de-energises when the
input signal goes below
the trip point
A red LED indicates the
state of the relay, whilst a green
LED indicates the condition
of the power supply. The
frequency relays monitor
their own power supply so no
auxiliary power is necessary.
ORDERING INFORMATION
Product Code Input V
Nominal Freq. Options
M200-F1C 230v 50Hz
|
|
|
TECHNICAL
SPECIFICATION
INPUT
Rated value Un 57.8<500V+
25%
Rated Frequency 50/60/400
Hz
Burden <25 VA
Overload 1.5 x Un continuous
2 x Un for 3 seconds
SETPOINT
Range 50Hz nominal Adjustable
40 to 60Hz
Range 60Hz nominal Adjustable
50 to 70Hz
Range 400Hz nominal Adjustable
360 to 440Hz
Differential 50 & 60Hz
Adjustable 0.3 to 3Hz
Differential 400Hz Adjustable
3 to 30Hz
Repeatability Better
than 0.5% of full span
Operating time Typically
200 ms
AUXILIARY
All units self powered
WEIGHT & CASE SIZE
Single units Approx.
0.4kg. 55mm case
Combined units Approx.
0.6kg. 100mm case
OPTIONS
1. On all of the above
units an internally set time delay
is available for any
value between 1 & 10 seconds. To
order use the above code,
adding a D at the end of the
code, e.g. M200-F1U/D
7 seconds (state the fixed delay
period)
2. AC auxiliary in range
57.7 to 480 volts
3. Calibration at temperature
other than 23º C
4. To prevent nuisance
tripping when there is a slight
variation in the frequency,
the following option is
available The external
differential is replaced with an
external time delay On
these units the time delay is
adjustable from 200ms
to 10 seconds, and the
differential is fixed
at 1%.
M200-F1X Single or 3
phase under frequency
M200-F1Y Single or 3
phase over frequency
M200-F1W Single or 3
phase combined frequency
|
|