SELECTION
GUIDE
M200-MVU mVunder trip
M200-MVO mV over trip
M200-MVC mV combined
trip
TYPICAL APPLICATIONS
The mV trip relays will
accept DC millivolt signals from
shunts, sensors and transducers.
A common application
is to protect equipment from over
current in a DC charging
system. For example using a 400A
to 75mV shunt. The 75mV
signal is fed to the M200-MVO if
the customer wishes to
ensure the current does not exceed
300 amps then the MVO
trip would be set at 75 % (56.25mv).
If the current goes above
300 Amps the relay would energise.
As is common with all
the M200 relays, on over units the
relay energises when
the input signal exceeds the trip point
and on under units the
relay de-energises when the input
signal goes below the
trip point.
A red LED indicates the
state of the relay, whilst a green
LED indicates the condition
of the power supply.
OPTIONS
1.Adjustable time delay
max 30 seconds
2.AC auxiliary in the
range 577 to 480 volt
3.Calibration at temperature
other than 23º C
|
|
|
|