PHASE BALANCE RELAY

SELECTION GUIDE
M200-PB1 Detects phase loss & phase unbalance
M200-PB2 Detects phase loss, phase unbalance &
symmetrical under-voltage

TYPICAL APPLICATIONS
The M200-PB1 can detect the following conditions in
phase 3 or 4 wire systems. Phase Unbalance, Phase Loss,
Phase Reversal and Phase Sequence.
The phase balance relays are used to detect phase loss
and unbalance in systems using motors, generators,
heater elements, transformers etc. A Phase unbalance as
small as 10% in a 3 phase motor can cause the
temperature in the motor winding to increase by more
than 120%, correct setting of the PB1/PB2 will ensure this
does not occur. Protection against open phase
regenerated voltage, created if a single phase should fail
is also provided.
Customer adjustment of unbalanced voltage between 5 to
15% is provided along with time delay adjustment of
200ms to 10 seconds.
If the system being monitored is healthy, the relay is
energised, and the red LED will be illuminated. If a phase
unbalance greater than the pre-set level or phase loss /
reversal occurs, the relay de-energises after the time delay
period. The M200-PB2 provides all the protection features
of the PB1 with the additional benefit of having
symmetrical under voltage protection. This means that if
all the phase voltages remain balanced but drop below a
pre-set value, the relay will de-energise. The under
voltage is internally set. For standard units it is set at 85%
below the nominal voltage, but this value can optionally
be between 70% and 90%


TECHNICAL SPECIFICATION

INPUT
Rated value Un 57.8<500V± 25%
Frequency 50/60/400 Hz
Burden <2VA
Overload 1.5x Un
2x Un
SETPOINT
Range Adjustment 5 to 15% unbalanced voltage
Repeatability Better than 0.5% of full span
Under-voltage PB2 only, pre-set 85% of nominal voltage
(optional 90% to 70%)

Time delay Adjustable 200 ms to 10 sec

AUXILIARY
Self powered

WEIGHT& CASE SIZE Approx. 0.4kg. 55mm case

ORDERING INFORMATION
Product Code Un Input Freq. Option
M200-PB2 415 v 50Hz Under Volts at 70%


OPTIONS
1. Adjustable time delay max 30 seconds
2. Internal under voltage set between 90% to 70%
3. Calibration at nominal Hz 35….450Hz
4. Calibration at temperature other than 23º C