SELECTION
GUIDE
M200-PB1 Detects phase
loss & phase unbalance
M200-PB2 Detects phase
loss, phase unbalance &
symmetrical under-voltage
TYPICAL APPLICATIONS
The M200-PB1 can detect
the following conditions in
phase 3 or 4 wire systems.
Phase Unbalance, Phase Loss,
Phase Reversal and Phase
Sequence.
The phase balance relays
are used to detect phase loss
and unbalance in systems
using motors, generators,
heater elements, transformers
etc. A Phase unbalance as
small as 10% in a 3 phase
motor can cause the
temperature in the motor
winding to increase by more
than 120%, correct setting
of the PB1/PB2 will ensure this
does not occur. Protection
against open phase
regenerated voltage,
created if a single phase should fail
is also provided.
Customer adjustment of
unbalanced voltage between 5 to
15% is provided along
with time delay adjustment of
200ms to 10 seconds.
If the system being monitored
is healthy, the relay is
energised, and the red
LED will be illuminated. If a phase
unbalance greater than
the pre-set level or phase loss /
reversal occurs, the
relay de-energises after the time delay
period. The M200-PB2
provides all the protection features
of the PB1 with the additional
benefit of having
symmetrical under voltage
protection. This means that if
all the phase voltages
remain balanced but drop below a
pre-set value, the relay
will de-energise. The under
voltage is internally
set. For standard units it is set at 85%
below the nominal voltage,
but this value can optionally
be between 70% and 90%
|
|
TECHNICAL
SPECIFICATION
INPUT
Rated value Un 57.8<500V±
25%
Frequency 50/60/400 Hz
Burden <2VA
Overload 1.5x Un
2x Un
SETPOINT
Range Adjustment 5 to
15% unbalanced voltage
Repeatability Better
than 0.5% of full span
Under-voltage PB2 only,
pre-set 85% of nominal voltage
(optional 90% to 70%)
Time delay Adjustable
200 ms to 10 sec
AUXILIARY
Self powered
WEIGHT& CASE SIZE Approx.
0.4kg. 55mm case
ORDERING INFORMATION
Product Code Un Input
Freq. Option
M200-PB2 415 v 50Hz Under
Volts at 70%
OPTIONS
1. Adjustable time delay
max 30 seconds
2. Internal under voltage
set between 90% to 70%
3. Calibration at nominal
Hz 35….450Hz
4. Calibration at temperature
other than 23º C
|
|