SELECTION
GUIDE
M200-RP1 Single phase
or 3 phase 4 wire
M200-RP3 3 phase 3 wire
TYPICAL APPLICATIONS
The M200 reverse power
relay is used to monitor
the direction of power
from AC generators. If the
current in the system
being monitored is reversed,
to a value greater than
the customer adjustable pre-
set limit, the relay
will energise.
The adjustable trip point
is 2 to 20% of input
current. An adjustable
time delay of 0 to 20 seconds
is provided. Correct
setting of the trip point and
time delay will ensure
protection against motoring
in the event of a generator
failure and prevent
tripping due to transients
encountered during
synchronising.
A red LED indicates the
state of the relay and a
green LED indicates the
condition of the power
supply
OPTIONS
1. Adjustable time delay
max 30 seconds
2. AC auxiliary in range
57.7 to 480 volts
3. Calibration at nominal
Hz 35 450Hz
4. Calibration at temperature
other than 23 C
|
|
TECHNICAL
SPECIFICATION
INPUT
Rated value Un 57.8 <500V
± 25%
Rated value In C. T operated
1 or 5A amp direct
connection 0.2 to 10A
Frequency 50 / 60 /400Hz
Burden <3VA voltage <
0.5 VA current
Overload 1.5 x Un 2 x
In continuous
2x Un 10 x In for 3
seconds
SETPOINT
Range 2% to 20% reverse
current
Repeatability Better
than 0.5% of full span
Time delay Adjustable
200ms to 20 sec
Hysteresis 1%
AUXILIARY
All units self powered
WEIGHT & CASE SIZE Approx.
0.6kg. 100mm case
ORDERING INFORMATION
Product Code In Input
Un Input Freq.
M200-RP3 1 Amp 400V 50Hz
|
|