REVERSE POWER RELAY

SELECTION GUIDE

M200-RP1 Single phase or 3 phase 4 wire
M200-RP3 3 phase 3 wire

TYPICAL APPLICATIONS

The M200 reverse power relay is used to monitor
the direction of power from AC generators. If the
current in the system being monitored is reversed,
to a value greater than the customer adjustable pre-
set limit, the relay will energise.
The adjustable trip point is 2 to 20% of input
current. An adjustable time delay of 0 to 20 seconds
is provided. Correct setting of the trip point and
time delay will ensure protection against motoring
in the event of a generator failure and prevent
tripping due to transients encountered during
synchronising.
A red LED indicates the state of the relay and a
green LED indicates the condition of the power
supply

OPTIONS
1. Adjustable time delay max 30 seconds
2. AC auxiliary in range 57.7 to 480 volts
3. Calibration at nominal Hz 35 450Hz
4. Calibration at temperature other than 23 C


TECHNICAL SPECIFICATION

INPUT
Rated value Un 57.8 <500V ± 25%
Rated value In C. T operated 1 or 5A amp direct
connection 0.2 to 10A
Frequency 50 / 60 /400Hz
Burden <3VA voltage < 0.5 VA current
Overload 1.5 x Un 2 x In continuous
2x Un 10 x In for 3 seconds

SETPOINT
Range 2% to 20% reverse current
Repeatability Better than 0.5% of full span
Time delay Adjustable 200ms to 20 sec
Hysteresis 1%

AUXILIARY
All units self powered

WEIGHT & CASE SIZE Approx. 0.6kg. 100mm case

ORDERING INFORMATION
Product Code In Input Un Input Freq.
M200-RP3 1 Amp 400V 50Hz