ORDERING
INFORMATION
Product Code M200-ST3
Normal running speed 1800
rpm
Number of teeth on flywheel
50
Magnetic pick up output
voltage 10 volt pk-pk
TYPICAL APPLICATIONS
The M200-ST3 is most
commonly used to detect the
speed of engines used
in generating sets. The pick-up,
situated close to the
flywheel, produces a high frequency
pulse train directly
proportional to the number of teeth
passing it. The frequency
is converted by the ST3 into a
mA signal directly proportional
to the rotational speed
of the flywheel.
The relay provides the
user with the following
adjustments, which allows
the control of start up and
normal running and protects
against over and under
speeds of the generator.
Adjustment of crank
speed 10 to 50%
Adjustment of under
speed 50 to 100%
Adjustment of over speed
100 to 133 %
A mA output signal proportional
to input frequency.
Typical start-up as follows
-
When the speed of the
motor reaches the crank's set-
point, the crank relay
energises, disengaging the crank
starter. When the under
speed set-point is reached, the
under speed relay is
energised and the motor is now in
the normal running condition
with all relays energised.
Should an under or over
speed condition occur the
appropriate relay is
de-energised. Two other safety
features are incorporated;
if the pick-up sensor input
lead breaks the over
speed relay will de-energise also
the crank relay will
only de-energise when the input
frequency goes below
20% of the set-point. The mA
output signal can be
fed to digital or analogue meters
scaled in speed, or to
provide a control signal to a PLC
etc.
|
|
TECHNICAL
SPECIFICATION
INPUT
Pulses 5V-75V peak to
peak
Frequency 1000-10000
Hz (speed of rotation
RPM x number of teeth
/ 60)
Open circuit protection
Over-speed relay de-energised
OUTPUT
Rated value 0-1mA = 133%
of nominal speed
Load resistance < lOk
Ohm
Calibration Value 0.75mA
= 100% of nominal speed
SETPOINT
Range Crank 10 to 50%
Under 50 to 100%
Over 100 to 130%
Repeatability Better
than 0.5% of full span
Hysteresis 2% (under,
over) crank resets at
20% setting
Operating time Typically
200 ms
AUXILIARY
DC Voltage 24 VDC ±20%
WEIGHT& CASE SIZE Approx.
0.5kg. l00mm case
NOTE: The 3 relays in
this product are single pole changeover.
The remainder of this
specification is as per general
specification on page
3.
SELECTION GUIDE
M200-ST3 Speed sensing
relay
OPTIONS
1. Calibration at temperature
other than 23º C
2. Set-points are factory
set. Specify frequency of
crank; under speed and
over speed settings required.
|
|