SELECTION
GUIDE
M200-PLL 1 generator 1
bus or 2 generators
M200-PLD 1 generator 1
bus with dead bus
facility
Both units can be used
on Single or 3 phase systems.
TYPICAL APPLICATIONS
The M200-PLL & PLD are
synchronising check relays,
also known as paralleling
relays. They are used to
ensure at two AC supplies
are synchronised. For a
system to be synchronised,
frequency, phase angle and
voltage have to within
pre-set limits.
The M200-PLL can monitor
either mains bus bar and
incoming generator or
two generators.
The PLL has customer
adjustment of the differential
voltage between 10 to
30%. This voltage corresponds to
6 to 20 electrical degrees.
The unit compares the input
voltage and phase relationship
of the bus bar to that of
the generator when the
signal is within the pre-set limits,
the relay energises.
The M200-PLD operates
as the M200-PLL but has the
additional feature of
the dead bus facility. This enables
the relay to energise
with a generator supply only, which
is a common requirement
when mains failure occurs.
|
|
TECHNICAL
SPECIFICATION
INPUT
Rated value Un 57.8<500Vą
25%
Frequency 50 /60/400
Hz
Burden <4VA terminals
marked GEN
<2VA terminals marked
BUS
Overload 1.5x Un continuous
10x Un for 3 seconds
SETPOINT
Range Adjustable 10%
to 30% of
nominal system voltage
(6-20 electrical degrees)
Repeatability Better
than 0.5% of full span
Differential Fixed at
5%
Operating time Typically
500ms
AUXILIARY
Both units self powered.
WEIGHT & CASE SIZEApprox.
0.6kg. 100mm case
ORDERING INFORMATION
Product
Code System Voltage Freq. Options
M200-PLD 400V 50Hz Cal
at 350C
OPTION
1.
Calibration at temperature other than 230 C
|
|