SYNCHRONISING CHECK RELAY

SELECTION GUIDE

M200-PLL 1 generator 1 bus or 2 generators
M200-PLD 1 generator 1 bus with dead bus
facility
Both units can be used on Single or 3 phase systems.

TYPICAL APPLICATIONS

The M200-PLL & PLD are synchronising check relays,
also known as paralleling relays. They are used to
ensure at two AC supplies are synchronised. For a
system to be synchronised, frequency, phase angle and
voltage have to within pre-set limits.
The M200-PLL can monitor either mains bus bar and
incoming generator or two generators.
The PLL has customer adjustment of the differential
voltage between 10 to 30%. This voltage corresponds to
6 to 20 electrical degrees. The unit compares the input
voltage and phase relationship of the bus bar to that of
the generator when the signal is within the pre-set limits,
the relay energises.
The M200-PLD operates as the M200-PLL but has the
additional feature of the dead bus facility. This enables
the relay to energise with a generator supply only, which
is a common requirement when mains failure occurs.


TECHNICAL SPECIFICATION

INPUT
Rated value Un 57.8<500Vą 25%
Frequency 50 /60/400 Hz
Burden <4VA terminals marked GEN
<2VA terminals marked BUS
Overload 1.5x Un continuous
10x Un for 3 seconds
SETPOINT
Range Adjustable 10% to 30% of
nominal system voltage
(6-20 electrical degrees)
Repeatability Better than 0.5% of full span
Differential Fixed at 5%
Operating time Typically 500ms

AUXILIARY
Both units self powered.

WEIGHT & CASE SIZEApprox. 0.6kg. 100mm case

ORDERING INFORMATION
Product Code System Voltage Freq. Options
M200-PLD 400V 50Hz Cal at 350C

OPTION
1. Calibration at temperature other than 230 C