THERMOCOUPLE TRIP RELAY

SELECTION GUIDE


M200-TJU J type thermocouple under trip
M200-TJO J type thermocouple over trip
M200-TKU K type thermocouple under trip
M200-TKO K type thermocouple over trip


TYPICAL APPLICATIONS

Designed to monitor thermocouples and provide a relay
signal if the temperature being monitored exceeds the pre-
set limit. J and K type thermocouples inputs are available
covering a wide range of temperatures. As is common with
all the M200 relays, on over units the relay energises when
the input signal exceeds the trip point and on under units
the relay de-energises when the input signal goes below the
trip point. A red LED indicates the state of the relay, whilst
a green LED indicates the condition of the power supply.

ORDERING INFORMATION
Product Code Temp range Aux Freq Options
M200-TJO 0-300ºC 120V 60Hz 0-30 sec T/D

OPTIONS
1. Adjustable time delay max 30 seconds
2. AC auxiliary in the range 57.7 to 480 volts
3. Calibration at temperature other than 23º C


TECHNICAL SPECIFICATION

INPUT
Type J Fe/const Min range 0-185ºC (min span 10mV)
Max range 0-870ºC (max span 50mV)
Type K NiCr/NiAl Min range 0-245ºC (min span 10mV)
Max range 0-1230ºC (max span 50mV)
Thermocouple
break protection Upscale energise
Cold junction
Compensation Automatic over range 0-50 C
Overload 10 x Input continuous

SETPOINT
Range Over Adjustable 40% to 120% for both
voltage and current input
Range Under Adjustable 0% to 80% for both
voltage and current input

Repeatability Better than 0.5% of full span
Time delay Adjustable 200ms to 10 seconds
Differential Fixed 2%

AUXILIARY
AC Voltage 115/230/400V
± 25% / 45-65Hz / 2VA
DC Voltage 24 volt (± 20% / galvanically isolated)
<3 Watt
WEIGHT &
CASE SIZE Approx. 0.4kg 55mm case