AUXILIARY
AC voltage 115 or 230 volts (±15%)
DC voltage 12 / 24 / 48 / 110 / 125 volts
RELAY OUTPUT (optional)
Pulsed output W.h or VAr.h or VA.h or A.h User
progammable import or export
COMMUNICATION
Serial communication RS485 output Modbus protocol
Baud Rate Programmable
2400,4800,9600,19200,38400,57600
Parity Odd, Even or No parity
Auto Detection RS485
ENVIRONMENTAL
Working Temperature 0 to +60 deg C
Storage Temperature -30 to +65 deg C
Temperature Coefficient 0.01% per deg C
Relatively Humidity 0-95% non condensing
Warm up time 1 min.
Shock 20G in 3 planes
ENCLOSURE
Fixing Snap on to Din rail
35 x 7.5mm complies with
DIN-EN 50022
Mounting Any position
Enclosure Code Case IP 50 / terminals IP30
Complies with IEC 529
BS5490 DIN 40050
APPLIED STANDARDS
General IEC 688 BSEN60688, BS4889, IEC 359
EMC Emissions BSEN50081/1 Immunity BSEN50082/2
Safety IEC1010, BSEN601010
INSULATION
Test Voltage 4kV RMS 50Hz for 1 min between input, case, auxiliary,
RS485 3kV RS485 / 1.5kV Relay
Impulse Test EMC 5kV transient complying with IEC 801/EN 55020 HF
Surge withstand IEC 801 / EN55020 ANSI C37.90A
Interference EHF 2.5kV 1MHz complying with IEC255-4
Protection Class II Complying with IEC348
|