INPUT
Rated Un Direct connected voltages between 57.8
and 600 v.
Standard voltages offered :-
63.5/110 V, 69.3 / 120 V, 120 / 208 V,
220/380 V, 230 / 400 V, 240 / 415 V,
277 / 480 V, for 3 ph 4 w
110 V, 120 V, 380 V, 400 V, 415 V, 440V,
480 V, 3 ph 3 w
Range 2-120% Un
Burden 0.5VA per phase
Overload 1.5 x Un continuous
4 x Un for 1 second
Rated In 1 or 5 amp
Range 0-120%
Burden 0.5VA per phase
Overload 4 x In continuous
50 x In for 1 second
Frequency 50 / 60 Hz nominal range
45/65Hz
SYSTEMS
M560-AT1 Single phase
M560-AT1-3 Single phase 3 wire
M560-AT4 3 phase 3 wire unbalanced load
M560-AT9 3 phase 4 wire unbalanced load
M570-AT2 3 phase 3 wire balanced load
M570-AT3 3 phase 4 wire balanced load
ACCURACY
Specified@ 23 °C 10%-Un 10%-In
Parameters unless stated Class 0.3% to IEC 688
Volts and Amps Class 0.25% to IEC 688
Frequency Class 0.1Hz to IEC 688
Power Factor Class 1.0% to IEC 688
Active Energy 1% of reading IEC 1036
Reactive Energy 1% of reading IEC 1036
ANALOGUE OUTPUTS
3 outputs programmable to any 3 parameters.
(except energy measurements W.h VAr.h VA.h A.h)
Rated value (software selectable)
0-1mA into <10kOhm load
0-5mA into <2kOhm load
0-10mA into <1kOhm load
0-20mA into <0.5kOhm load
4-20mA into <0.5kOhm load
0-10 volts >1kOhm load
Accuracy is relative to a standard 20mA or 10V output.
When outputs are specified on order, the
accuracy will applicable to that output.
Load influence <0.1%
Ripple <0.5% peak-peak at full load
Response time <400 msec for 0-99% at full load
Overload <2 x rated value at full load
No load voltage <18 volts
|
|
AUXILIARY
AC voltage 115V, 230V or 277V (±15%)
DC voltage 12 / 24 / 48 / 110 / 125 volts
RELAY OUTPUT (optional)
Pulsed output W.h or VAr.h or VA.h or A.h User
progammable import or export
COMMUNICATION
Serial communication RS485 output Modbus protocol
Baud Rate Programmable
2400,4800,9600 and 19200
Parity Odd, Even or No parity
Auto Detection RS485
ENVIRONMENTAL
Working Temperature 0 to +60 deg C
Storage Temperature -30 to +65 deg C
Temperature Coefficient 0.01% per deg C
Relatively Humidity 0-95% non condensing
Warm up time 1 min.
Shock 20G in 3 planes
ENCLOSURE
Fixing Snap on to Din rail
35 x 7.5mm complies with
DIN-EN 50022
Mounting Any position
Enclosure Code Case IP 50 / terminals IP30
Complies with IEC 529
BS5490 DIN 40050
APPLIED STANDARDS
General IEC 688 BSEN60688, BS4889, IEC 359
EMC Emissions BSEN50081/1 Immunity BSEN50082/2
Safety IEC1010, BSEN601010
INSULATION
Test Voltage 4kV RMS 50Hz for 1 min between input, case, auxiliary, RS485
3kV RS485 / 1.5kV Relay
Impulse Test EMC 5kV transient complying with IEC 801/EN 55020 HF
Surge withstand IEC 801 / EN55020 ANSI C37.90A
Interference EHF 2.5kV 1MHz complying with IEC255-4
Protection Class II Complying with IEC348
APPROVALS
UL. C-UL, CSA Pending
|