ACCURACY
Active Energy 1% of reading
(IEC 1036)
Accuracy to IEC 1036
Class 1
BS 5685 (IEC 521)
ANALOGUE OUTPUT
Accuracy Class 1%
Rated value 0-1mA into
<5 kOhm
Rated value 0-20mA into
<250 Ohms
OUTPUT RELAY
kW.h pulsed output Normally
open volt free contact 50V
150mA 5W ac/dc
Pulse rate Standard 1
pulse per kW.h ( 1 pulse = 10
kW.h on higher CT &
VT ratios
Pulse duration Standard
250 msec other values optional on request
Led flash rate 0.1 kW.h
per flash
ENVIROMENTAL
Working Temperature 0
to +60 deg C
Function Temperature
- 25 to +70 deg C
Storage Temperature -55
to +85 deg C
Temperature Coefficient
0.01% per deg C
Relative Humidity 0-95%
non condensing
Warm up time 1 min.
Shock 30G in 3 planes
ENCLOSURE
Standard DIN case 96
x 96 x 98mm
Panel mount Via retaining
side brackets and screws
Panelcutout 92 + 0.8mm
x 92 + 0.8mm
Material Black Polycarbonate
complying with
UL 94 VO
Enclosure code IP54
100mm Trans.case 100
x 70 x 112mm light grey polycarbonate
complying with UL 94
VO
Fixing Snap on Din rail
35 x 7.5 mm complies with
DIN 50022 BS 5584
Enclosure code Case IP50
/ terminals IP 30 complies with
IEC 529 BS 5490 DIN
40050
Terminals Both case,
Screw terminal for 2 x 0.5-3.5mm
|
|