2 WIRE TRANSMITTER AC CURRENT TRANSDUCER

TECHNICAL SPECIFICATION
INPUT
Rated value In 1 or 5 Amp C.T. connected
0.5-10 Amp direct connected
Working range 10-125% In
Rated Frequency 40- 400 Hz
Frequency influence 0.005 % / Hz
Overload continuous 4 x In
Overload for 1 sec. 50 x In

Accuracy 0.2%
Linearity <0.1%
Repeatability ± 0.05% of span
Common mode rejection 130dB
Input impedance 0.1 Ohm
Response time <250mSec 0-90% at full load

OUTPUT
DC current 4-20mA
Drive voltage 24 volts (max. 35 volts)
DC volt drop 12 volts dc max.
Output load change effect 0.1% up to RL max.
Max. loop load (Ohms) V supply - 12V
0.02

ADJUSTMENT
Zero ± 1%
Span ± 10%

ISOLATION
Between input & output 4kV RMS 50Hz for 1 minute

ENVIRONMENTAL
Working temperature 0 to +60 deg C
Functional temperature -25 to +70 deg C
Storage temperature -55 to +85 deg c (100 ppm / °C)
Relative humidity 95% non condensing
Class of climate HSE complying with DIN 40040
-3 complying with VDE/VDI3540

WEIGHT & CASE
M700-AL1 Approx. 0.2 kg. 55mm case


SELECTION GUIDE
M700-AL1 2 Wire transmitter, ave. sensing, RMS calibrated.

TYPICAL APPLICATIONS
The M700 series are 2 wire transmitters.
The M700-AL1 converts the A.C. Input current signal to a
4-20mA D.C. Output. The output is directly proportional to the
input signal.

2 Wire transmitters like the M700-AL1, obtain the power to
operate from the 4-20mA output circuit to which they are
connected, and therefore require no separate auxiliary supply.
The M700-AL1 is average sensing RMS calibrated current
transmitter. 2 Wire transmitters have an advantage over
conventional auxiliary powered transducer, because no separate
auxiliary is required, savings in the cost of providing a separate
auxiliary supply and wiring are made. The above units are used to
measure current in energy management systems, switchboards,
generator and telemetery controls. Isolation of 4kV is provided
between the input and output signal, allowing the output to be fed
to conventional analogue meters, digital meters, PLC, and computer
systems.


ORDERING INFORMATION
Product Code Input In Output Options
M700-AL1 5A 4-20mA

OPTIONS
1. Calibration at temperature other than 23°C