Input (accuracy range)
Un 28V to 330V L-N (48V to 570V L-L)
Burden < 0.5VA
In 0.5A to 6A via CT
Burden < 0.5VA
Frequency 45Hz to 65Hz
Secondary of CTs must be connected to earth
Overload
800V L-L indefinitely
In x 10 for 1 sec
Accuracy
Voltage 0.5% +/- 2 digits
Current 0.5% +/- 2 digits
Power (W,VAr,VA) 1.0% +/- 2 digits
Power Factor 1% of range
Frequency 0.1 Hz
Energy IEC 1036 Class 1
Auxiliary Voltage
100V to 440V ac (45Hz to 65Hz)
100V to 420V dc
Burden: < 10VA
Display
Digits 3 lines 9999
Digit size 14.2mm 7 segment
Update time 1 second
|