Read Coils
(code 1)
M550, M560, M570 (revision 0.3.00.00
and later) and M850 models.
Returns
one byte of data.
Each bit represents the exception state of the corresponding condition
(structure).
Read Holding
(4X) Registers (code 3)
Returns
a specified number of consecutive system registers (IEEE754 floating point).
Read Input
(3X) Registers (code 4)
Returns a specified number of consecutive measurement registers (IEEE754 floating point).
N.B.
In some products, the order that the registers appear can be altered
to suit a user's needs.
In most products, the measurement registers are duplicated (mapped)
into the 4X area.
Pre-set Multiple Holding (4X) Registers (code 16)
Writes data to a specified number of consecutive system registers.
Report Slave
ID (code 17)
This function returns the status of an instrument, The returned
packet consists of 10 or more, four byte floating point numbers.(IEEE754)
Special Codes (65-72 and 101-108 inc)
Replaces codes 30 to 39 incl. in older models.
These codes are specifically implemented to facilitate the programming
of the instruments and transducers.
Send
Modbus register order (65)
M550, M560, M570 (revision 0.3.00.00 and later) and M850 models.
Replaces code 30 in older models.
Send a string of data to set the order of the registers.
Retrieve
relay channels parameters (code 66)
M550, M560, M570 (revision 0.3.00.00 and later) and M850 models.
Replaces code 31 in older models.
Request ALL register order data.
Send
relay channels parameters (code 103)
M550, M560, M570 (revision 0.3.00.00 and later) and M850 models.
Replaces code 42 in older models.
Sends 8, 16 byte structures representing the parameters
for the 8 conditions that can be attached to each relay installed.
Retrieve
relay channels parameters (code 104)
M550, M560, M570 (revision 0.3.00.00 and later) and M850 models.
Replaces code 41 in older models.
Requests 8, 16 byte structures representing the parameters
for the 8 conditions that can be attached to each relay installed.
Send
Endian for floating point format (code 108)
M550, M560 revision 0.4.01.00 (Release date 2012) and M850 models dated after August 2011.
Sends 1 byte to set the format for floating point data.
Exception
Codes
A normal response from a slave is the echoing of the function
code and the supplying of the data that is requested.
Exceptions are reported in the response from a slave node by setting
the msb of the function code and inserting the applicable error
code in the data field. Only the last example below will result
in an exception being reported to the master node.
If the slave does not receive the query due to a communication
error, no response is returned.The master node will eventually process
a time-out condition for the query.
If the slave receives the query, but detects a communication
error (parity or CRC), no response is returned. The master program
will eventually process a time-out condition for the query.
If the slave receives the query without a communication
error but cannot handle it (e.g. a request to read a non-existent
register), the slave will return an exception response informing
the master of the nature of the error.
The error codes that could be returned in the data field are:
01 - Illegal or Unknown Function
02 - Illegal Data Address
03 - Illegal Data value
|