Clear Demand Registers
Clear the contents of the ALL demand registers. (any value can be used)
For M550 and M560 transducers, the write functions require the General Pass Code to be valid.


Sample Coding
Slave Address = 1
Writing To 4X Registers - code 16 (10 hex)


Message Packet To SLAVE
01 10 00 12 00 02 04 00 00 00 00 73 7A

Response Packet From SLAVE
01 10 00 12 00 02 E1 CD