Reset EEPROM
Reset the EEPROM data to default values. This function does not reset or
clear the calibration data stored when the factory calibrated the unit.
In addition to the General
Pass Code being valid, another code, found below, needs to be sent as data
with this function
For the M560 transducers, the write functions require the General
Pass Code to be valid.
Sample Coding
Slave Address = 1
Writing To 4X Registers - code 16 (10 hex)
Message Packet To SLAVE
01 10 00 2C 00 02 04 46 9B 7E 00 B4 E5
N.B. Code 46 9B 7E 00 = 19903
Response Packet From SLAVE
01 10 00 2C 00 02 80 01