Set Node Address
Set the address of a new node or change the address of an existing one.
For M550 and M560 transducers, the write functions require the General Pass Code to be valid.

Sample Coding
Slave Address = 1
Writing To 4X Registers - code 16 (10 hex)
Changing node number from 1 to 23 (41 B8 00 00)

Message Packet To SLAVE
01 10 00 16 00 02 04 41 B8 00 00 E6 90

Response Packet From SLAVE
01 10 00 16 00 02 A0 0C