System Settings
Read or set the system Voltage and/or Current
The monitored system's Voltage and Current can be set up or verified via the RS485 Modbus link.
For M550 and M560 transducers, the write functions require the General Pass Code to be valid.

Sample Coding 1
Slave Address = 1
Writing To 4X Registers - code 16 (10 hex)
Changing system Voltage to 220V

Message Packet To SLAVE
01 10 00 00 00 02 04 43 5C 00 00 26 39
N.B. 43 5C 00 00 = 220

Response Packet From SLAVE
01 10 00 00 00 02 41 C8

Sample Coding 2
Slave Address = 1
Writing To 4X Registers - code 16 (10 hex)
Changing system Current to 800A

Message Packet To SLAVE
01 10 00 02 00 02 04 44 48 00 00 E6 90
N.B. 44 48 00 00 = 800

Response Packet From SLAVE
01 10 00 02 00 02 E0 08