System Settings
Read or set the System Current
The monitored system's Current can be set up or verified via the RS485 Modbus link.


Sample Coding
Slave Address = 1
Writing To 4X Registers - code 16 (10 hex)
Changing system Current to 800A

Message Packet To SLAVE
01 10 00 02 00 02 04 44 48 00 00 E6 90
N.B. 44 48 00 00 = 800

Response Packet From SLAVE
01 10 00 02 00 02 E0 08