M100 Power Range

 

M100 Power Range

Download brochure

M100 specification

Environment
Working temperature 0 to +60 °C
Functional temperature -25 to +70 °C
Storage temperature -55 to +85 °C
Temperature coefficient 0.02% per °C (100ppm/°C)
Relative humidity 95% non condensing
Class of climate HSE complying with DIN40040-3 complying with VDE/VDI3540

Accuracy
Class ±0.2 % complying with IEC688
Calibration temperature 23°C
Temperature coefficient 0.01% / °C (100 ppm / °C)
Stability 0.05 % per annum non cumulative
Warm up time <15 min Outputs
Rated value
See individual product pages.

Load resistance (current output)
1mA <15 kOhm
5mA <3 kOhm
10mA <1.5 kOhm
20mA < 0.75kOhm
4-20mA < 0.75kOhm
Load resistance (voltage output)
1V, 5V & 10V >1 kOhm
(M100-VA1,VA3) 1V, 5V & 10V > 50kOhm 

Load influence < 0.1 %
Ripple < 0.5% peak-peak at full load
Response time < 200 ms for 0-99 % at full load
Overload < 2 x rated value at full load
No load voltage < 27 V Approvals
U.L. Approval File No E157034

Insulation
Test Voltage:
4kV RMS 50Hz 1min. between Input/Case/Auxiliary/Output
Impulse Test:
EMC 5kV transient complying with IEC801/EN55020
HF interference:
EHF 2.5kV 1MHz complying with IEC255-4
Protection:
Class II complying with IEC348 BS4753/DIN57411/VDE 0411

Enclosure
Fixing - Snap on to DIN rail 35 x 7.5 mm complying with DIN-EN50022 BS5584
Mounting - Any position
Enclosure Code - Case IP50/terminals IP30 complying with IEC529 BS5490 DIN40050

Applied Standards
General IEC688/BS6253/VDE/VDI2192
Safety EN61010-1 DIN57411/VDE0411 ANSI C37
Surge withstand IEC801/EN55020 ANSI C37-90a
Radio screening RFI degree N complying with VDE0875
EMC Emissions EN61326-1
Immunity EN61326-2

M100 Active Power Transducer

Selection Guide
M100-WA1 Single phase
M100-WA2 3 phase 3 wire balanced load
M100-WA3 3 phase 4 wire balanced load
M100-WA4 3 phase 3 wire unbalanced load
M100-WA5 3 phase 4 wire unbalanced load
M100-WA6 3 phase 3 wire balanced load externally connected reverse CTs
M100-WA7 3 phase 3 wire balanced load internally reversed CTs

Typical Applications
The M100-WA series measure active power in single, three phase three or four wire balanced and unbalanced systems.
Using the time division multiplier circuit means that they can be used over a wide range of input waveforms. The D.C. Output signal is directly proportional to the instantaneous power being measured.
Typical applications include the measurement of power in switchboards, power stations, generating sets etc.
The high isolation of 4kV as with all the M100 series, allow these watt transducers to be connected to a variety of measuring and control devices and systems, such as analogue meters, PLC, computers, data loggers, digital instruments and telemetry systems.
Both auxiliary powered and self powered versions of each type are available, it is recommended to use an auxiliary powered version if the system being measured has voltage variations in excess of ± 20%.

Ordering Information
Product Code I/P In Un O/P Range Aux Freq Opt.
M100-WA5 800/5A 230v 0-20mA 600kW 230v 50Hz

Options
1. Non standard inputs / outputs only as far as technically acceptable.
2. A.C. Auxiliary in range 57.7 to 450 volts
3. Calibration at nominal Hz 35.....450Hz
4. Calibration at temperature other than 23°C

Technical Specification

Input

Rated value In 1 or 5 Amp C.T. connected
0.5-10 Amp direct connected
Rated value Un 57.8 < 600 volt
Power consumption <1 VA voltage
<0.2 VA current
Working range 0-125% Un auxiliary powered
75-125% Un self powered
0-150% In
Rated Frequency 50 / 60 / 400 Hz
Frequency influence 0.005 % / Hz
Overload continuous 4 x In 1.5 x Un
Overload for 1 sec. 50 x In 2 x Un

Output

Rated value mA 0-1/5/10/20 & 4-20mA
Rated Value Volts 0-5 / 10 & 1-5 V

Adjustments

Zero ± 2%
Span ± 10%

Auxiliary

A.C. Voltage 115 / 230 / 400 V (± 25% / 45-65 Hz / < 2VA)
D.C. Voltage 24 / 48 / 110 V (± 20% / galvanically isolated / <3 W)

Weight and Case

M100-WA1,2,3,6,7 Approx. 0.6kg. 100mm case
M100-WA4,5 Approx. 0.8kg. 100mm case

M100 Reactive Power Transducer

Selection Guide
M100-XA1 Single phase
M100-XA2 3 phase 3 wire balanced load
M100-XA3 3 phase 4 wire balanced load
M100-XA4 3 phase 3 wire unbalanced load
M100-XA5 3 phase 4 wire unbalanced load
M100-XA6 3 phase 3 wire unbalanced load
M100-XA7 3 phase 3 wire balanced load internally reversed CTs

Typical Applications
The M100-XA series measure reactive power in single, three phase three or four wire balanced and unbalanced systems.
Using the time division multiplier circuit means that they can be used over a wide range of input waveforms.
The D.C. Output signal is directly proportional to the instantaneous reactive power being measured.
Typical applications include the measurement of reactive power in switchboards, power stations and generating sets etc.
The high isolation of 4kV as with all the M100 series, allows these VAr transducers to be connected to a variety of measuring and control devices and systems, such as analogue meters, PLC, computers, data loggers, digital instruments and telemetry systems.
Both auxiliary powered and self powered versions of each type are available.
It is recommended to use an auxiliary powered version if the system being measured has voltage variations in excess of ± 20%.

Ordering Information
Product code I/P In Un O/P Range Aux. Freq. Opt.
M100-XA4 400/5 400 0-20mA 300kVAr 120 60Hz

Options
1. Non standard inputs / outputs only as far as technically acceptable.
2. A.C. Auxiliary in range 57.7 to 450 volts
3. Calibration at nominal Hz 35.....450Hz
4. Calibration at temperature other than 23°C

Technical Specification

Input

Rated value In 1 or 5 Amp C.T. connected
0.5-10 Amp direct connected
Rated value Un 57.8 < 600 volt
Power consumption <1 VA voltage
<0.2 VA current
Working range 0-125% Un auxiliary powered
75-125% Un self powered
0-150% In
Rated Frequency 50 / 60 / 400 Hz
Overload continuous 4 x In 1.5 x Un
Overload for 1 sec. 50 x In 2 x Un

Output

Rated value mA 0-1/5/10/20 & 4-20mA
Rated Value Volts 0-5 / 10 & 1-5 V

Adjustments

Zero ± 2%
Span ± 10%

Auxiliary

A.C. Voltage 115 / 230 / 400 V (± 25% / 45-65 Hz / < 2VA)
D.C. Voltage 24 / 48 / 110 V (± 20% / galvanically isolated / <3W)

Weight and Case

M100-XA1,2,3,6,7 Approx. 0.6kg. 100mm case
M100-XA4,5 Approx. 0.8kg 100mm case

M100 Phase Angle Transducer

Selection Guide
M100-PA1 Single phase 4 quadrants
M100-PA2 3 phase 3 or 4 wire balanced 2 quadrants
M100-PA3 3 phase 3 or 4 wire balanced 4 quadrants
M100-PV1 Single phase 4 quadrants phase angle between two voltages

Typical Applications
The M100-PA series of phase angle transducers measure the phase angle between current and voltage.
They can be used on single and three phase three or four wire balanced systems and are ideal for optimising power factor correction.
The M100-PV2 measures the phase angle between two voltage supplies and provides a D.C. output signal proportional to the phase angle between the voltages.

Ordering Information
Product code I/P In Un O/P Range Aux. Freq.Opt.
M100-PA2 5Amp 400V ± 45° 120V 60Hz

Options
1. Non standard inputs / outputs only as far as technically acceptable.
2. A.C. Auxiliary in range 57.7 to 450 volts
3. Calibration at nominal Hz 35.....450Hz
4. Calibration at temperature other than 23°C

Technical Specification

Input

Rated value In 1 or 5 Amp C.T. connected
0.5-10 Amp direct connected
Rated value Un 57.8 < 600 volt
Power consumption <1 VA voltage (aux powered)
<2.5 VA voltage (self powered)
<0.2 VA current
Working range 15-125% Un auxiliary powered
75-125% Un self powered
10-150% In
Measuring range ± 45 / 60 / 90 / 180° M100-PA1
± 45 / 60° M100-PA2 ± 90 / 180° M100-PA3
Rated Frequency 50 / 60 / 400 Hz
Frequency influence 0.005 % / Hz
Overload continuous 4 x In 1.5 x Un
Overload for 1 sec. 50 x In 2 x Un

Accuracy

± 1 degree

Output

Rated value mA 0-1/5/10/20 & 4-20mA
Rated Value Volts 0-5 / 10 & 1-5 V

Adjustments

Zero ± 2%
Span ± 10%

Auxiliary

A.C. Voltage 115 / 230 / 400 V (± 25% / 45-65 Hz / < 2VA)
D.C. Voltage 24 / 48 / 110 V (± 20% galvanically isolated / <3W)

Weight and Case

Approx. 0.6 kg. 100mm case