Demand Period
Read
or Set the demand period. The legal value is an integer value between 3 and
60 minutes.
For M550 and M560 transducers, the write functions require the General
Pass Code to be valid.
Sample Coding
Slave Address = 1
Writing To 4X Registers - code 16 (10 hex)
Value to write = 15 minutes
Message Packet To SLAVE
01 10 00 08 00 02 04 41 70 00 00 E7 EE
N.B. Value 41 70 00 00 = 15
Response Packet From SLAVE
01 10 00 08 00 02 C0 0A