M550/M560/M570 New Node Setup
When a new transducer (M550/M560/M570) is delivered its address is set to 1. All
transducers on a network will respond if address 254 is used by a master node
or program.
Two options for connection the transducer to a network are :-
1) Disconnect or power
off all nodes. Introduce the new node to the network and power up alone. Talk
to the node by using address 254. When the node responds, reprogram its address
to the required one. Power up all the other nodes
2) Using the MultiView program, available on request or from our website, re-program
its address to the required one and then introduce it to the network.
Sample Coding
Slave Address = 1
Writing To 4X Registers - code 16 (10 hex)
Changing node number from 1 to 23 (41 B8 00 00)
Message Packet To SLAVE
01 10 00 16 00 02 04 41 B8 00 00 E6 90
Response Packet From SLAVE
01 10 00 16 00 02 A0 0C