Analogue Outputs Min/Max

Sample Coding

WRITE
Slave Address = 1
Write 6 consecutive 4X Registers - code 16
First 3 floating point values are channel 1-3 Maximum setting
Last 3 floating point values are channel 1-3 Minimum setting
All channels are 0 - 20mA nominal.

Analogue Channel 1 (Maximum = 120% Minimum = -120%)
Max = 24mA
Min = -24mA

Analogue Channel 2 (Maximum = 100% Minimum = 20%)
Max = 20mA
Min = 4mA

Analogue Channel 3 (Maximum = 100% Minimum = 0%)
Max = 20mA
Min = 0mA

Message Packet To SLAVE
01 10 00 72 00 0C 18 42 F0 00 00 42 C8 00 00 42 C8 00 00 C2 F0 00 00 41 A0 00 00 00 00 00 00 95 CB
N.B. 42 F0 00 00 = 120, 42 C8 00 00 = 100, C2 F0 00 00 = -120, 41 A0 00 00 = 20

Response Packet From SLAVE
01 10 00 72 00 0C 60 17