Set General Pass Code
Set the General Pass Code in the node (code found below).
This enables other
functions to alter the node settings.
Use this function with data set to zero to clear the General Pass Code.
If the General Pass Code is updated with an invalid number all pass codes will
be invalidated.
N.B. The pass code remains in its current state until one of the following
-
1) The transducer/meter
is re-booted
2) The General Pass
Code is cleared
3) There has been
no 4X register write functions for 6 minutes.
Sample Coding
Slave Address = 1
Writing To 4X Registers - code 16 (10 hex)
Message Packet To SLAVE
01 10 00 42 00 02 04 46 93 AC 00 EE 23
N.B. 46 93 AC 00 = 18902
Response Packet From SLAVE
01 10 00 42 00 02 E1 DC