Relay Assignment
Relay Assignment - Relay Mode
Read or set the relay assignment.
To set, write to this address with one of the following values –

1 = IMPORT W.h
2 = EXPORT W.h

Set Relay Pulse Width to zero to turn the relay off

Sample Coding
Slave Address = 1
Writing To 4X Registers - code 16 (10 hex)
Value to write = 1 (kW.h IMPORT)

Message Packet To SLAVE
01 10 00 2A 00 02 04 3F 80 00 00 7C 34

Response Packet From SLAVE
01 10 00 2A 00 02 60 00