M100-WA2 Watt Transducer

£ 211.45

The M100-WA2 series measure active power in a 3 phase  3 wire  balanced load systems.

A full range of transducers is available on our main site. For enquiries please contact sales@multitek-ltd.com 

 

Description

The M100-WA series measure active power in single, 3 phase 3 or 4 wire balanced and unbalanced systems. Using the time division multiplier circuit means that they can be used over a wide range of input waveforms. The D.C. Output signal is directly proportional to the instantaneous power being
measured.

The above units are used to measure voltage in energy management systems, switchboards, generator and telemetry controls.

Isolation of 4kV is provided between the input and output signal, allowing the output to be fed to conventional analogue meters, digital meters, PLC, and computer systems.

A full range of transducers is available on our main site. For enquiries please contact sales@multitek-ltd.com 

 

Additional information

Weight 0.7 kg
Dimensions 12 × 11 × 8.5 cm

Downloads

Brochure (Whole Range)

Specification

TECHNICAL SPECIFICATION

INPUT
Rated value Un 57.8 to 600 V (specify nominal voltage when ordering)
Power consumption <1 VA
Working range 0-125% Un
Rated Frequency 50 / 60
Frequency influence 0.005 % / Hz
Overload continuous 1.5 x Un
Overload for 1 sec. 4 x Un

OUTPUT
Rated value  4-20mA

ADJUSTMENT
Zero ± 2%
Span ± 10%

AUXILIARY
A.C. Voltage 57.7V /63.5V /69.3V/120V /139V /220V /230V /240V /277V /380V /400V /415V
(± 25% / 45-65Hz / <2 VA)

Full Product Range

Current, Voltage, Watts, Vars, Frequency, Power Factor, DC to DC, Resistance, Tap Position, RTD Temperature, Thermocouple Temperature.