M200-PLD Synchronising Check Relay (Dead Bus)

£ 125.00

The M200-PLL is a synchronising check relay, also known as paralleling relay.

A full range of relays is available on our main site. For enquiries please contact sales@multitek-ltd.com 

Description

The M200-PLD is a synchronising check relay, also known as paralleling relay. They are used to ensure that two AC supplies are synchronised.
For a system to be synchronised, frequency, phase angle and voltage have to within pre-set limits.
The M200-PLD can monitor either mains bus bar and incoming generator or two generators. The PLD has customer adjustment of the differential voltage between 10 to 30%. This voltage corresponds to 6 to 20 electrical degrees. The unit compares the input voltage and phase relationship of the bus bar to that of the generator when the signal is within the pre-set limits, the relay energises. The M200-PLD operates as the M200-PLL but has the additional feature of the dead bus facility. This enables the relay to energise with a generator supply only, which is a common requirement when mains failure occurs.

A full range of relays is available on our main site. For enquiries please contact sales@multitek-ltd.com 

 

Additional information

Weight 0.7 kg
Dimensions 12 × 11 × 8.5 cm
Input Voltage (L-L)

100V, 110V, 120V, 208V, 220V, 380V, 400V, 415V, 440V, 460V, 480V, 600V

Specifications

Technical Specification

Input

Rated value Un 57.8<500V± 25%
Frequency 50 /60/400 Hz
Burden <4VA terminals marked GEN
<2VA terminals marked BUS
Overload 1.5x Un continuous
10x Un for 3 seconds

Setpoint

Range Adjustable 10% to 30% of nominal system voltage (6-20 electrical degrees)
Repeatability Better than 0.5% of full span
Differential Fixed at 5%
Operating time Typically 500ms

Auxiliary

Both units self powered.

Weight and Case

Approx. 0.6kg. 100mm case