Description
The M200 reverse power relay is used to monitor
the direction of power from AC generators. If the
current in the system being monitored is reversed,
to a value greater than the customer adjustable preset
limit, the relay will energize.
The adjustable trip point is 2 to 20% of input
current. An adjustable time delay of 0 to 20 seconds
is provided. Correct setting of the trip point and
time delay will ensure protection against motoring
in the event of a generator failure and prevent
tripping due to transients encountered during
synchronizing.
A red LED indicates the state of the relay and a
green LED indicates the condition of the power supply
A full range of relays is available on our main site. For enquiries please contact sales@multitek-ltd.com