PPH Divisor
Setting
Read
or Set the desired divisor for the Energy Counters.
For M552 transducers, the write functions require the
General
Pass Code to be valid.
Divide by:-
1000, 100, 10, 1, 0.1, 0.01, 0.001 can be used.
The following is dependent on the number of pph (5000 max)
A
value of 1 puts the transducer into A.h mode.
A value of 1000 puts the transducer into kA.h mode.
A value of 0.001 puts the transducer into mA.h mode.
Sample Coding
Slave Address
= 1
A.h divisor update: Register Address 10h
Writing To 4X Registers - code 16 (10 hex)
Value to write = 1
Message Packet To
SLAVE
01 10 00 0E 00 02
04 3F 80 00 00 7F DF
N.B. Value 3F 80 00 00 = 1
Response Packet From SLAVE
01 10 00 0E 00 02 20 0B