M100 Voltage Range

 

M100 Voltage Range

Download brochure

M100 specification

M100 specification

Environment
Working temperature 0 to +60 °C
Functional temperature -25 to +70 °C
Storage temperature -55 to +85 °C
Temperature coefficient 0.02% per °C (100ppm/°C)
Relative humidity 95% non condensing
Class of climate HSE complying with DIN40040-3 complying with VDE/VDI3540

Accuracy
Class ±0.2 % complying with IEC688
Calibration temperature 23°C
Temperature coefficient 0.01% / °C (100 ppm / °C)
Stability 0.05 % per annum non cumulative
Warm up time <15 min

Outputs
Rated value
See individual product pages.

Load resistance (current output)
1mA <15 kOhm
5mA <3 kOhm
10mA <1.5 kOhm
20mA < 0.75kOhm
4-20mA < 0.75kOhm
Load resistance (voltage output)
1V, 5V & 10V >1 kOhm
(M100-VA1,VA3) 1V, 5V & 10V > 50kOhm

Load influence < 0.1 %
Ripple < 0.5% peak-peak at full load
Response time < 200 ms for 0-99 % at full load
Overload < 2 x rated value at full load
No load voltage < 27 V

Approvals
U.L. Approval File No E157034

Insulation
Test Voltage:
4kV RMS 50Hz 1min. between Input/Case/Auxiliary/Output
Impulse Test:
EMC 5kV transient complying with IEC801/EN55020
HF interference:
EHF 2.5kV 1MHz complying with IEC255-4
Protection:
Class II complying with IEC348 BS4753/DIN57411/VDE 0411

Enclosure
Fixing - Snap on to DIN rail 35 x 7.5 mm complying with DIN-EN50022 BS5584
Mounting - Any position
Enclosure Code - Case IP50/terminals IP30 complying with IEC529 BS5490 DIN40050

Applied Standards
General IEC688/BS6253/VDE/VDI2192
Safety EN61010-1 DIN57411/VDE0411 ANSI C37
Surge withstand IEC801/EN55020 ANSI C37-90a
Radio screening RFI degree N complying with VDE0875
EMC Emissions EN61326-1
Immunity EN61326-2

AC Voltage

M100 AC Voltage Transducer

Selection Guide
M100-VA1 1 ph. self powered average sensing RMS calibrated
M100-VL1 1 ph. auxiliarypowered average sensing RMS calibrated
M100-VR1 1 ph. auxiliarypowered true RMS sensing RMS calibrated
M100-VA3 3 ph. self powered average sensing RMS calibrated
M100-VL3 3 ph. auxiliary powered average sensing RMS calibrated

Typical Applications
The M100 series voltage transducers are designed to measure A.C. voltage in single and three phase systems. They convert the A.C. signal to a D.C. output that is directly proportional to the input.
The M100-VA1 VA3 are self powered (no auxiliary required), average sensing, RMS calibrated voltage transducers with mA or voltage outputs.
The M100-VL1 VL3 are average sensing RMS calibrated, live zero voltage transducers. Auxiliary is required to provide power so that a 4mA output signal is present when the input is zero.
The M100-VR1 is true RMS sensing and RMS calibrated allowing measurements of distorted waveforms up to 9th harmonic with a crest factor of 5. The VR1 is typically used in voltage measurement where distorted waveform is common such as thyristor drives.
These transducers are used to measure voltage in energy management systems, switchboards, generator and telemetery controls.
Isolation of 4kV is provided between the input and the output, allowing the ouput to be fed to conventional analogue meters, digital meters, PLC, and computer systems.

Ordering Information
Product Code Input In Output Aux Freq. Options
M100-VA1 230V 4-20mA 230V 50Hz

Options
1. Non standard inputs / outputs only as far as technically acceptable.
2. A.C. Auxiliary in range 57.7 to 450 volts
3. Calibration at nominal Hz 35.....450Hz
4. Calibration at temperature other than 23°C

Technical Specification

Input

Rated value Un 57.8 <100 / 110 <600 V
Power consumption <1.5 VA (VA1, VA3)
<1 VA (VL1, VL3, VR1)
Working range 15-125% Un (VA1, VA3)
0-125% Un (VL1, VL3, VR1)
Rated Frequency 50 / 60 / 400 Hz
Frequency influence 0.005 % / Hz
Overload continuous 1.5 x Un
Overload for 1 sec. 4 x Un (VL1 VL3 VR1 )
2 x Un (VA1 VA3)

Output

Rated value mA 0-1/5/10/20mA (VA1, VA3)
Rated value mA 1/5/10/20 & 4-20mA (VR1)
Rated value mA 4-20mA (VL1)

Rated Value volts 0-5 / 10 V (VA1, VA3)
Rated value volts 0-5 / 10 & 1-5 V (VR1)
Rated value volts 1-5 V (VL1 VL3)

Adjustments

Zero No adjustment (VA1,VA3)
Zero ± 2% (VR1,VL1)
Span ± 10% (VA1,VA3,VR1,VL1,VL3)

Auxiliary

A.C. Voltage 115 / 230 / 400 V(± 25% / 45-65Hz / <2 VA)
D.C. Voltage 24 / 48 / 110 V (± 20% /galvanically isolated / < 3 W)
Note M100-VA1 & VA3 are self powered.

Weight and Case

M100-VA1 Approx. 0.3 kg. 55mm case
M100-VL1,VR1 Approx. 0.4 kg. 55mm case
M100-VA3 Approx. 0.6 kg. 100mm case
M100-VL3 Approx. 0.7 kg. 100mm case

Special AC Voltage

M100 Special AC Voltage Transducer

Selection Guide
M100-VS1 Suppressed zero voltage auxiliary powered
M100-VX1 1 ph. aux. powered ave. sensing RMS calibrated
M100-VX33 ph. aux. powered ave. sensing RMS

Typical Applications
The M100-VS1 is a self powered voltage transducer.
The suppression allows the transducer to accurately measure a voltage system over a narrow band either side of a nominal voltage.
The range can be between ± 10% to ± 30% which can be specified when ordering.
Typical application is to display the voltage on an analogue meter with an expanded scale. This allows the user to read small changes in the voltage in a single or three phase system.
The output could also be fed to a computer that could then control the voltage of the system, to ensure that it stays within the narrow band.
The M100-VX1 and M100-VX3 are essentially the same as the M100-VA1 and M100-VA3, but have auxiliaries which allow the working range to be 0-125% rather than 10-125%.
Used where the average sensing of voltage is required from 0 to 125% of the nominal voltage.

Ordering Information
Product Code Input Un Output Aux Freq. Option
M100-VS1 110V ± 15% 20mA - 50Hz

Options
1. Non standard inputs / outputs only as far as technically acceptable.
2. A.C. Auxiliary in range 57.7 to 450 volts
3. Calibration at nominal Hz 35.....450Hz
4. Calibration at temperature other than 23°C

Technical Specification

Input

Rated value Un 57.8V <100V / 110V <600V
Power consumption < 1 VA (VX1, VX3)
<1.5 VA (VS1)
Working range 0-125% Un (VX1, VX3)
10-30% Un (VS1)
Rated Frequency 50 / 60 / 400 Hz
Frequency influence 0.005 % / Hz
Overload continuous 1.5 x Un
Overload for 1 sec. 2 x Un

Output

Rated value mA 0-1 / 5 / 10 / 20mA (VX1, VX3)
Rated value mA 1/5/10/20 & 4-20mA (VS1)

Rated value volts 0-5 / 10 V (VX1, VX3)
Rated value volts 0-5 / 10 V & 1-5 V (VS1)

Adjustments

Zero No adjustment (VX1, VX3)
Zero ± 2% (VS1)
Span ± 10% (VX1, VX3, VS1)

Auxiliary

A.C. Voltage 115 / 230 / 400 V(± 25% / 45-65Hz / <2 VA)
D.C. Voltage 24 / 48 / 110 V (± 20% galvanically isolated / < 3 W)
Note M100-VS1 is self powered

Weight and Case

M100-VS1,VX1 Approx. 0.4 kg. 55mm case
M100-VX3Approx. 0.7 kg.

DC Current / Voltage

M100 DC Current or Voltage 4kV or 1.5kV Isolation Transducers

Selection Guide
M100-DA1 DC current input 4kV isolation
M100-DV1 DC voltage 20mV..11.9V input 4kV isolation
M100-DV2 DC voltage 12V..600V input 4kV isolation

M100-DA1I DC current input 1.5kV isolation
M100-DV1I DC voltage 20mV..11.9V input 1.5kV isolation
M100-DV2I DC voltage 12V..600V input 1.5kV isolation

Typical Applications
These isolators isolate the DC input signal from the DC output signal, which is directly proportional to the input signal. There are two levels of isolation offered, the M100-DA1/DV1/DV2 have 4kV isolation and the M100-DA1I/DV1I/DV2I have 1.5kV isolation.
A wide range of both D.C. Current and voltage inputs are offered.
Typically these isolators can be used to prevent earth loops, which occur when an earthed measuring source is connected to a computer or data logger that is also earthed. Another common use is to provide isolation on the inputs to a PLC. All of the above isolators have either A.C. or D.C. auxiliaries which means they have an advantage over loop powered units, in that if for any reason the output lead should become disconnected, the input will not be saturated.

Ordering Information
Product code Input In Output Aux Freq. Options
M100-DA1I 1mA 4-20mA 230V 50Hz

Options
1. Non standard inputs / outputs only as far as technically acceptable.
2. A.C. Auxiliary in range 57.7 to 450 volts
3. Calibration at temperature other than 23°

Technical Specification

Input

Rated value In ± 0-1mA...10A M100-DA1 / DA1I
Voltage drop 20mV
Rated value Un ± 20mV......11.9V M100-DV1 / DV1I
Impedance 100 kOhm / volt
Rated value Un ± 12 V.......600 V M100-DV2 / DV2I
Impedance 10 kOhm / volt
Working range ± 125% In
Overload continuous 4 x In M100-DA1 (upto 20A max)
Overload continuous 1.5 x Un M100-DV1 / DV2

Output

Rated value mA 0-1/5/10/20 & 4-20mA
Load resistance 12/2.4/1.2/0.6 kOhm
Rated value volts 0-5 / 10 & 1-5 V

Adjustments

Zero ± 2%
Span ± 10%

Auxiliary

A.C. Voltage 115 / 230 / 400 V (± 25% / 45-65Hz / < 2VA)
D.C. Voltage 24 / 48 / 110 V (± 20% /galvanically isolated / <3W)

Weight and Case

Approx. 0.4 kg. 55mm case

Insulation

See M100 Specification.
M100-DA1/DV1/DV2 4kV
M100-DA1I/DV1I/DV2I 1.5kV RMS 50Hz 1 min between input / case / output

Triple Current / Voltage

M100 DC Current or Voltage 1 Input 3 Output Transducers

Selection Guide
M100-DM3 One input three outputs

Typical Applications
The M100-DM3 takes 1 DC input signal and provides 3 isolated outputs all directly proportional to the input. The outputs can all be of the same D.C. value or different. Typically this product is used to prevent earth loops between measuring devices.
For example
An M100-DM3 could have its input signal provided by a M100-WA4 watt transducer with 4-20mA output.
The 3 outputs from the M100-DM3 could be as follows.
Output A: 4-20mA fed to a PLC.
Output B: 0-20mA fed to an analogue meter scaled in kW.
Output C: 1-5 volt fed to a chart recorder.

Ordering Information
Product Code Input In Output Aux. Freq. Options
M100-DM3 1mA A= 1mA 230V 50Hz B=4-20mA C=10V

Options
1. Non standard inputs / outputs only as far as technically acceptable.
2. A.C. Auxiliary in range 57.7 to 450 volts
3. Calibration at temperature other than 23°C

Technical Specification

Input

Rated value In ± 0-1 / 5 / 10 / 20 & 4-20mA
Voltage drop 20mV
Rated value Un ±20mV......10V
Impedance 100 kOhm / volt
Working range ±125% In
Overload continuous 4 x In
Overload continuous 1.5 x Un

Output

Rated value mA 0-1/5/10/20 & 4-20mA
Load resistance 10/2/1/0.5 kOhm
Rated value volts 0-5 / 10 & 1-5 V

Adjustments

Zero ± 2%
Span ± 10%

Auxiliary

A.C. Voltage 115 / 230 / 400 V (± 25% / 45-65Hz / < 2VA)
D.C. Voltage 24 / 48 / 110 V (± 20% / galvanically isolated / <3W)

Weight and Case

Approx. 0.4 kg. 100mm case

Insulation

See M100 Specification.
Test voltage
1.5 kV between Input/ Output/Case
500 volt between each output