Environment
Working temperature 0 to +60 °C
Storage temperature -40 to +85 °C
Relative humidity 85% non condensing
Applied Standards
EMI/EMC
Surge: EN61000-4-5:2005 - Class B
ESD: EN61000-4-2:2008 - Class B
Fast Transients: EN61000-4-4:2004 + A1:2010 - Class B
Magnetic Field: EN61000-4-8:2009 - Class A
Voltage Dips: EN61000-4-11:2004 - Class B & C
Conducted RF: EN61000-4-6:2008 - Class A
Radiated RF: EN61000-4-3:2006
+ A1:2007 + A2:2010 - Class A
Flicker & Inrush: EN61000-3-3:2008
Harmonics: EN61000-3-2:2005
+ A1:2008 + A2:2009 - Class A
Conducted Emission: EN550011:2009 A1:2010 - Class A
Radiated Emission: EN550011:2009 A1:2010 - Class A
Safety
Voltage between I/P and O/P: 60664-1 - 4kV
Impulse between I/P and O/P: 60664-1 - Level IV
Single Fault: IEC 61010-1 - Level IV
Leakage Current: UL 508 <3.5mA
Environmental
Cold: IEC 60068-2-1
Dry Heat: IEC 60068-2-2
Vibration: IEC 60068-2-6 - 5g
Repetitive Shock: IEC 60068-2-27 - 40g 6ms
Non-Repetitive Shock: IEC 60068-2-27 - 30g 15ms
Enclosure
Fixing - Snap onto DIN rail 35mm symmetrical
Mounting - Any position
Enclosure Code - IP20 Terminals, IP30 Housing
Dimensions: 17.5mm x 59mm x 97mm
Weight: 60g (2 Terminals) 65g (3 Terminals)
Relay Output
Type: SPDT
Material: Ag-Alloy
Contact resistance: 100mOhm
Rating AC: 250V 8A Resistive load
Rating DC: 5A 30V Resistive load
Electrical life: 100,000 operations at rated load
Mechanical life: 10,000,000 operations rated load
Operating time: 10mS Max
Dielectric strength:
Between coil and contacts: 5kV RMS 1min
Between adjacent contacts: 1kV RMS 1min
Insulation resistance: 1000MOhm at 500V DC
Operating temperature: -40 to +85 °C
Approval: UL, EN/IEC, VDE
Selection Guide
M220-V1 Single phase
M220-V33 Three Phase Three Wire
M220-V34 Three Phase Four Wire
Description
The M220 Ac voltage relay provides voltage monitoring and protection in both single and 3 phase systems. Used in applications such as mains failure, regulation of power supplies and to protect voltage sensitive equipment, the relay protects against both under and over voltage conditions and operates when the externally adjustable trip points are reached. Either a differential or time delay adjustment is available, depending on the model. The differential control provides adjustment from 1- 15% which ensures that the parameter being measured returns to a percentage above or below the trip point before the relay returns to its original state. Time delay is adjustable from 100mS to 10S. The M220 voltage relay also features phase sequence detection, protecting against phase reversal.
Operation
When the signal being measured is between the over and under set points the relay is energised and both fault indicator LEDs are green. If the signal increases past the over set point, or decreases below the under set point, the relay will de-energise and the appropriate fault LED will change to red. If an incorrect phase sequence is detected both fault LEDs will flash red.
Power Supply
The voltage relays monitor their own power supply so auxiliary power is not necessary. A green LED indicates a supply is present. The relays feature an adjustable power supply, allowing flexible selection of the connected nominal voltage.
Two ranges are Available when ordering:
1. 110V - 120V - 208V - 230V - 240V - 277V
2. 380V - 400V - 415V - 440V - 460V - 480V
Each range provides 6 common supply voltages for selection.
Technical Specification
Rated Supply (Un) 1: 110V - 277V
Rated Supply (Un) 2: 380V - 480V
Frequency: 45Hz - 65Hz /400 Hz
Burden: <2.1 VA
Overload: 1.5x Un continuous
Range under Adjustable: 75% to 100% Un
Range over Adjustable: 100% to 125% Un
Repeatability: Better than 0.5% of full span
Differential: Adjustable 1 to 15%
Time Delay: Adjustable 100ms to 10 sec
Operating time: Typically 100ms
All units self powered.
Ordering information available in the brochure.
Selection Guide
M220-F1 Single phase
Description
The M220 series frequency relays are designed to monitor the frequency of a system, if the frequency deviates outside the customer adjustable preset limits the relay will operate. The user is provided with adjustment of both the trip point of frequency being monitored and a differential / time delay adjustment (depending on model).
Operation
When the frequency being measured is between the over and under set points the relay is energised and both fault indicator LEDs are green. If the signal increases past the over set point, or decreases below the under set point, the relay will de-energise and the appropriate fault LED will change to red.
Power Supply
The frequency relays monitor their own power supply so auxiliary power is not necessary. A green LED indicates a supply is present.
The relays feature a power supply with a wide input range, operating on supplies from 110V to 480V, and is available to order in three standard ranges:
1. 50Hz (40Hz to 50Hz Under, 50Hz to 60Hz over).
2. 60Hz (50Hz to 60Hz Under, 60Hz to 70Hz over).
3. 400Hz (360Hz to 400Hz Under, 400Hz to 440Hz over).
Custom ranges are also available on request.
Technical Specification
Rated Supply (Un) 1: 110V - 480V
Frequency: 50Hz / 60Hz /400 Hz
Burden: <2.1 VA
Overload: 1.5x Un continuous
Range 50Hz: 40Hz to 50Hz Under
50Hz to 60Hz Over
Range 60Hz: 50Hz to 60Hz Under
60Hz to 70Hz Over
Range 400Hz: 360Hz to 400Hz Under
400Hz to 440Hz Over
Repeatability: Better than 0.5% of full span
Differential: 50Hz/60Hz - 0.3Hz to 3Hz
400Hz - 3Hz to 30Hz
Time Delay: Adjustable 100ms to 10 sec
Operating Time: Typicall 100ms
All units self powered.
Ordering information available in the brochure.
Selection Guide
M220-PBS Three Phase Three Wire
Description
The M220-PBS can detect the following conditions in 3 phase 3 wire system: Phase Unbalance, Phase Loss, Phase reversal, Phase Sequence, and Symmetrical under voltage. The M220-PBS is used to detect phase loss and unbalance in a system using motors, generators, heater elements, transformers etc. A phase unbalance as small as 10% in a 3 phase motor can cause the temperature in the motor winding to increase by more than 120%, but correct setting of the M220-PBS will ensure this does not occur. Protection against open phase regenerated voltage, created if a single phase should fail, is also provided. Customer adjustment of the unbalanced voltage from 5% to 15% is provided along with time delay adjustment of 100mS to 10S. The M220-PBS has the additional benefit of having symmetrical under voltage protection. This means that if all 3 phase voltages remain balanced, but drop below a preset voltage, the relay will de-energise. The under voltage is externally set from 90% below the nominal voltage, to 70% below the nominal voltage.
Operation
All LEDs will be green when the percentage unbalance measured is below the unbalance set point, and all three phase voltages are above the symmetrical under voltage set point. If the unbalance measured is above the set point the unbalance LED will turn to red and the relay will de-energise. If the symmetrical under voltage is blow the set point, the under voltage LED will turn to red, and the relay will de-energise. If an incorrect phase sequence is detected both fault LEDs will flash red.
Power Supply
The voltage relays monitor their own power supply so auxiliary power is not necessary. A green LED indicates a supply is present. The relays feature an adjustable power supply, allowing flexible selection of the connected nominal voltage.
The following voltages are selectable from the front panel:
110V / 120V / 208V / 230V / 240V
277V / 380V / 400V / 415V / 480V
Technical Specification
Rated Supply (Un) 1: 110V - 480V
Frequency: 45Hz - 65Hz
Burden: <2.1 VA
Overload: 1.5x Un continuous
Range Unbalance: 5% to 15%
Range Symmetrial Under: 90% to 70%
Repeatability: Better than 0.5% of full span
Differential: 1% Internally set
Time Delay: Adjustable 100ms to 10 sec
Operating Time: Typicall 100ms
All units self powered.
Ordering information available in the brochure.