M600 kWh Meter
M600 Introduction
The M600 kWh meter comes in a standard DIN 96 x 96 case.
Its mechanical counter is 7 digits long and is non resetable.
When the counter exceeds 9999999 it rolls over to zero.
The M600 can be supplied with a pulsed output allowing it to be connected to remote counters, PLCs data loggers and computers and a mA output proportional to the instantaneous power being measured.
Options
1. Pulsed output.
2. Analogue output of instantaneous power
3. Non standard pulsed width.
4. Calibration at temperature other than 23 °C
5. Calibration at nominal Hz 35 ..... 450 Hz.
Product code:
DIN 96 x 96 with Mechanical Counter
Single Phase..............M600-WM1
3ph 3W bal. Load.....M600-WM2
3ph 4W bal. Load.....M600-WM3
3ph 3W unbal. Load..M600-WM4
3ph 4W unbal.load.....M600-WM9
Ordering Information Example
Product Code M600-WM4
C.T. ratio 500/5 AMP
Frequency 50Hz
Auxiliary Voltage 230V
Options Pulsed output
M600 specification
Input (accuracy range)
Rated Un:
57V to 500V specify nominal voltage.
Range 80-120% Un
Burden <0.2VA per phase
Rated In:
1A or 5A
Range 10-120% In
Burden <0.5VA per phase
Overload
Overload 1.5 x Un continuous
4 x Un for 1 second
Overload 4 x In continuous.
50 x In for 1sec
Frequency - nominal range 50/60 Hz (45/65Hz working)
Systems
Single phase
3 phase 3 wire balanced load
3 phase 4 wire balanced load
3 phase 3 wire unbalanced load
3 phase 4 wire unbalanced load
Accuracy
Active Energy 1% of reading (IEC1036)
Accuracy to IEC1036 Class 1 BS5685 (IEC521)
Auxiliary Voltage
115V AC or 230V AC or 400 V AC
Current And Voltage Ratios
Internally selectable
Analogue Output
Accuracy Class 1%
Rated value 0-1mA into <5 kOhm
Rated value 0-20mA into <250 Ohms
Insulation
Test Voltage:
Test Voltage 4 kV RMS 50 Hz for 1 min (3kV if analogue output required)
Impulse Test:
Impulse Test EMC 5kV transient complying with IEC801/EN55020
HF interference:
EHF 2.5 kV 1MHz complying with IEC255-4
Protection:
Class II complying with IEC348/BS4743 DIN57411/VDE 0411
Environment
Working Temperature 0 to +60 °C
Function Temperature - 25 to +70 °C
Storage Temperature -55 to +85 °C
Temperature Coefficient 0.01% per °C
Relative Humidity 0-95% non condensing
Warm up time 1 min.
Shock 30G in 3 planes
Enclosure
Standard DIN case 96 x 96 x 98mm
Panel mount via retaining side brackets and screws
Panelcutout 92 + 0.8mm x 92 + 0.8mm
Material Black Polycarbonate complying with UL 94 VO
Enclosure code IP54
Applied Standards
Designed to IEC1036 accuracy BS5685 (IEC521)
Output Relay
kW.h pulsed output.
Normally open volt free contact 50V 150mA 5W ac/dc
Pulse rate - standard 1 pulse per kW.h ( 1 pulse = 10 kW.h on higher CT & VT ratios)
Pulse duration - standard 250 ms (other values optional on request )
Led flash rate - 0.1 kW.h per flash