M560 Introduction
The M560 PowerSig is a complete single phase or three phase multifunction AC power transducer, providing up to 3 analogue outputs and the option of an RS485 communication port.
Up-to 3 fully isolated analogue outputs are available. Most of the M560's measurements can be assigned to the outputs which can be either DC mA or DC volts. If PowerSig is purchased without the option of RS485 the user must specify which measurement is required for each output when ordering.
The M560 measures Voltages, Currents, Import/Export Power (W, VAr, VA), True Power Factor, Frequency, Import/Export Demands(Wd, VArd, VAd, Ad) and Import/Export Energy (W.h, VAr.h, VA.h, and A.h)
An option of pulsed output via a relay is offered. The pulsed output can be assigned to W.h, Var.h (import or export), A.h or VA.h.
Using the RS485 port and Modbus protocol, all measured quantities can be obtained, the system's parameters can be set up, important data can be saved to computer and the order of the Modbus registers themselves can be changed.
ORDERING INFORMATION
Example
Product Code M560-AT9
Nominal input voltage 230 / 400V AC
Nominal input current 5A AC
System Frequency 50Hz
Auxiliary 230V
Output 3 x 4-20mA
Option RS485 Modbus.
M560 specification
Input (accuracy range)
Rated Un:
Direct connected voltages between 57.8V and 600V.
Standard voltages offered :-
3ph 4w - 63.5/110V, 69.3/120V, 120/208V, 220/380V, 230/400V, 240/415V, 277/480V
3ph 3w - 110V, 120V, 380V, 400V, 415V, 440V, 480V
Range 2-120% Un
Rated In:
1A or 5A
Range 0 - 120%
Frequency 50 / 60 Hz nominal range
45/65Hz working
Overload
1.5 x Un continuous, 4 x Un for 1 second
4 x In continuous, 50 x In for 1 second
Burden
Un 0.5VA per phase
In 0.5VA per phase
Systems
M560-AT1 Single phase
M560-AT1-3 Single phase 3 wire
M560-AT4 3 phase 3 wire unbalanced load
M560-AT9 3 phase 4 wire unbalanced load
M560-AT2 3 phase 3 wire balanced load
M560-AT3 3 phase 4 wire balanced load
Accuracy
Specified@ 23 °C 10%-Un 10%-In
Parameters unless, otherwise stated, Class 0.3% to IEC 688 Volt Class 0.25% to IEC 688
Amps Class 0.25% to IEC 688
Frequency Class 0.1Hz to IEC 688
Power Factor Class 1.0% to IEC 688
Active Energy 1% of reading IEC 1036
Reactive Energy 1% of reading IEC 1036
Analogue Outputs
3 outputs programmable to any 3 parameters. (except energy measurements W.h VAr.h VA.h A.h)
Rated value (software selectable)
0-1mA into <10kOhm load
0-5mA into <2kOhm load
0-10mA into <1kOhm load
0-20mA into <0.5kOhm load
4-20mA into <0.5kOhm load
0-10 volts >1kOhm load
Accuracy is relative to a standard 20mA or 10V output.
When outputs are specified on order, the accuracy will applicable to that output.
Load influence <0.1%
Ripple <0.5% peak-peak at full load
Response time <400 msec for 0-99% at full load
Overload <2 x rated value at full load
No load voltage <18 volts
Auxiliary
AC 115V, 230V or 277V (±15%)
DC 12V/24V/48V/110V/125V
Approvals
UL. C-UL, CSA Pending
Insulation
Test Voltage:
4kV RMS 50Hz for 1 min between input, case, auxiliary, RS485 3kV RS485 / 1.5kV Relay
Impulse Test:
EMC 5kV transient complying with IEC 801/EN 55020 HF
Surge Withstand:
IEC801/EN55020 ANSI C37.90A
HF interference:
EHF 2.5kV 1MHz complying with IEC255-4
Protection:
Class II Complying with IEC348
Environment
Working Temperature 0 to +60 °C
Storage Temperature -30 to +65 °C
Temperature Coefficient 0.01% per °C
Relatively Humidity 0-95% non condensing
Warm up time 1 min.
Shock 20G in 3 planes
Enclosure
Fixing Snap on to Din rail 35 x 7.5mm complies with DIN-EN50022
Mounting Any position
Enclosure Code Case IP 50/terminals IP30
Complies with IEC529 BS5490 DIN40050
Applied Standards
General IEC688 BSEN60688, BS4889, IEC359
EMC Emissions EN61326-1
Immunity EN61326-2
Safety EN61010-1
Pulsed Output
Pulsed output W.h or VAr.h or VA.h or A.h
User progammable import or export
Communications
Serial communication RS485 using Modbus protocol
Baud Rate Programmable 2400,4800,9600,19200
Parity Odd, Even or None
Auto Detection RS485